Temperature Controller - Viessmann Vitosol 100-FM Technical Manual

Flat-plate collectors and vacuum tube collectors flat and pitched roof installation, and wall mounting
Table of Contents

Advertisement

Solar control units

Temperature controller

Part no. 7151 988
Suitable for:
■ Vitocell 300-B
■ Vitocell 300-V, type EVI
■ With a thermostatic system
■ With selector on the outside of the casing
■ Without sensor well
Suitable for sensor well, part no.7819 693
The sensor well is part of the standard delivery of DHW cylinders
from Viessmann.
0
7 2
1 3
Specification
Connection
IP rating
Setting range
Switching differential
6
VIESMANN
40
(cont.)
3-core lead with a cross-section of
2
1.5 mm
IP 41 to EN 60529
30 to 60 °C; can be changed to 110 °C
max. 11 K
Breaking capacity
6(1.5) A 250 V~
Switching function
with rising temperature from 2 to 3
DIN reg. no.
DIN TR 1168
Set of contact temperature sensors for energy cockpit
For capturing the temperature in the solar flow and return
Usage in conjunction with the Vitotronic 200, type HO2B:
■ Graphic display of energy consumption, solar utilisation, tempera-
ture stratification
■ Fault diagnosis
■ Visualisation of the operating state and solar yield via remote con-
trol, app and internet
Components:
■ 1 threaded elbow
■ 1 sensor well
■ 2 temperature sensors with leads (5.8 m long) and 1 plug
Vitocell 100-B, type CVB/CVBB
Vitocell 140/160-E
Vitocell 340/360-M
3
2
1
Part no.
ZK02 459
ZK02 460
ZK02 460
VITOSOL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents