Endress+Hauser Proline Promag 10 Brief Operating Instructions

Electromagnetic flowmeter
Hide thumbs Also See for Proline Promag 10:

Advertisement

Quick Links

KA00032D/06/EN/18.16
71321446
Products
Brief Operating Instructions
Proline Promag 10
Electromagnetic flowmeter
These Brief Operating Instructions are not intended to replace
the Operating Instructions provided in the scope of supply.
Detailed information is provided in the Operating Instructions
and the additional documentation on the CD-ROM supplied.
The complete device documentation consists of:
• These Brief Operating Instructions
• Depending on the device version:
– Operating Instructions and the Description of Device Funct.
– Approvals and safety certificates
– Special safety instructions in accordance with the approvals
for the device (e.g. explosion protection, pressure
equipment directive etc.)
– Additional device-specific information
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promag 10

  • Page 1 Solutions Services KA00032D/06/EN/18.16 71321446 Brief Operating Instructions Proline Promag 10 Electromagnetic flowmeter These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply. Detailed information is provided in the Operating Instructions and the additional documentation on the CD-ROM supplied.
  • Page 3: Table Of Contents

    Proline Promag 10 Table of contents Table of contents 1 Safety instructions ............. 4 1.1 Designated use .
  • Page 4: Safety Instructions

    European standards have been observed. • The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Operating Instructions. • The information specified on the warning notices, nameplates and connection labels fitted on the measuring device must be observed.
  • Page 5 The installation regulations, connection data and safety instructions provided in the Ex documentation must be observed. • Endress+Hauser will be happy to assist in clarifying any questions on approvals, their application and implementation.
  • Page 6: Safety Conventions

    Safety instructions Proline Promag 10 Safety conventions Warning! "Warning" indicates an action or procedure which, if not performed correctly, can result in injury or a safety hazard. Comply strictly with the instructions and proceed with care. " Caution! "Caution" indicates an action or procedure which, if not performed correctly, can result in incorrect operation or destruction of the device.
  • Page 7: Installation

    Proline Promag 10 Installation Installation Transporting to the measuring point • Transport the measuring device to the measuring point in the original packaging. • Do not remove the covers or caps until immediately before installation. 2.1.1 Transporting flanged devices DN  300 (12") To transport the unit, use slings slung around the process connections or use lugs (if available).
  • Page 8: Installation Conditions

    Installation Proline Promag 10 Installation conditions 2.2.1 Dimensions For the dimensions of the measuring device, see the associated Technical Information on the CD-ROM. 2.2.2 Mounting location The accumulation of air or formation of gas bubbles in the measuring tube can result in an increase in measuring errors.
  • Page 9 Proline Promag 10 Installation Partially filled pipes Partially filled pipes with gradients necessitate a drain-type configuration. The empty pipe detection (EPD) function offers additional protection by detecting empty or partially filled pipes. " Caution! Risk of solids accumulating! Do not install the sensor at the lowest point in the drain. It is advisable to install a cleaning valve.
  • Page 10 Installation Proline Promag 10 2.2.3 Orientation An optimum orientation helps avoid gas and air accumulations and buildup in the measuring tube. The measuring device, nevertheless, supplies a range of functions and tools to measure problematic fluids correctly: • Electrode cleaning circuitry (ECC) to prevent electrically conductive deposits in the measuring tube, e.g.
  • Page 11 Proline Promag 10 Installation Inlet and outlet runs If possible, install the sensor upstream from fittings such as valves, T-pieces, elbows, etc. The following inlet and outlet runs must be observed ³ ³ 2 x DN 5 x DN in order to meet accuracy specifications: •...
  • Page 12 Installation Proline Promag 10 2.2.5 Foundations, supports If the nominal diameter is DN  350 (14"), mount the sensor on a foundation of adequate load-bearing strength. " Caution! Risk of damage! Do not support the weight of the sensor on the metal casing.
  • Page 13: Installing The Promag E Sensor

    Proline Promag 10 Installation Installing the Promag E sensor " Caution! • The plates mounted on the two sensor flanges protect the PTFE which is turned over the flanges and, consequently, should not be removed until immediately prior to mounting the sensor.
  • Page 14 Installation Proline Promag 10 Promag E tightening torques for EN (DIN) Nominal diameter EN (DIN) Threaded Max. tightening torque [mm] Pressure rating [bar] fasteners [Nm] PN 40 4 × M 12 PN 40 4 × M 12 PN 40 4 × M 16 PN 40 4 ×...
  • Page 15 Proline Promag 10 Installation Promag E tightening torques for ANSI Nominal diameter ANSI Max. tightening torque PTFE Pressure rating Threaded [mm] [inch] [lbs] fasteners [Nm] [lbf · ft] ½" Class 150 4 × ½" 1" Class 150 4 × ½"...
  • Page 16: Installing The Promag H Sensor

    Depending on the application and length of the pipe, the sensor may have to be supported or additionally secured. The sensor must be secured if using plastic process connections. An appropriate wall mounting kit can be ordered separately from Endress+Hauser as an accessory. 2.4.1 Seals When mounting the process connections, make sure that the seals in question are free from dirt and centered correctly.
  • Page 17: Installing The Promag L Sensor

    Proline Promag 10 Installation Installing the Promag L sensor " Caution! • The protective covers mounted on the two sensor flanges (DN 25 to 300 / 1 to 12") are used to hold the lap joint flanges in place and to protect the PTFE liner during transportation.
  • Page 18 Installation Proline Promag 10 Promag L tightening torques for EN (DIN) Nominal diameter EN (DIN) Max. tightening torque Hard rubber Polyurethane PTFE [mm] Pressure rating Threaded [Nm] [Nm] [Nm] [bar] fasteners PN 10/16 4 × M 12 PN 10/16 4 × M 16 PN 10/16 4 ×...
  • Page 19 Proline Promag 10 Installation Nominal diameter EN (DIN) Max. tightening torque Hard rubber Polyurethane PTFE [mm] Pressure rating Threaded [Nm] [Nm] [Nm] [bar] fasteners 1800 PN 16 44 × M 52 1108 2000 PN 6 48 × M 39 2000 PN 10 48 ×...
  • Page 20 Installation Proline Promag 10 Promag L tightening torques for AWWA Nominal dia- AWWA Threaded Max. tightening torque meter fasteners Pressure Hartgummi Polyurethane PTFE rating [mm] [inch] [Nm] [lbf · ft] [Nm] [lbf · ft] [Nm] [lbf · ft] 28" Class D 28 ×...
  • Page 21 Proline Promag 10 Installation Promag L tightening torques for AS 4087 Nominal AS 4087 Threaded Max. tightening torque diameter fasteners Pressure rating Hard rubber Polyurethane PTFE [mm] [Nm] [Nm] [Nm] PN 16 12 × M 24 PN 16 12 × M 24 PN 16 12 ×...
  • Page 22: Installing The Promag P Sensor

    Installation Proline Promag 10 Installing the Promag P sensor " Caution! • The plates mounted on the two sensor flanges protect the PTFE which is turned over the flanges and, consequently, should not be removed until immediately prior to mounting the sensor.
  • Page 23 Proline Promag 10 Installation Promag P tightening torques for EN (DIN) Nominal diameter EN (DIN) Threaded Max. tightening torque [mm] Pressure rating [bar] fasteners [Nm] PN 40 4 × M 12 PN 40 4 × M 16 PN 40 4 × M 16 PN 40 4 ×...
  • Page 24 Installation Proline Promag 10 Promag P tightening torques for ANSI Nominal diameter ANSI Max. tightening torque PTFE Pressure rating Threaded [mm] [inch] [lbs] fasteners [Nm] [lbf · ft] 1" Class 150 4 × ½" 1" Class 300 4 × 5/8"...
  • Page 25 Proline Promag 10 Installation Nominal diameter Max. tightening torque [Nm] [mm] Pressure rating Threaded fasteners PTFE 8 × M 22 8 × M 20 12 × M 22 12 × M 20 12 × M 22 12 × M 22 12 ×...
  • Page 26: Installing The Promag W Sensor

    Installation Proline Promag 10 Installing the Promag W sensor " Caution! • The protective covers mounted on the two sensor flanges are used to hold the lap joint flanges in place and to protect the PTFE liner during transportation. Consequently, do not remove these covers until immediately before the sensor is installed in the pipe.
  • Page 27 Proline Promag 10 Installation Promag W tightening torques for EN (DIN) Nominal diameter EN (DIN) Max. tightening torque [Nm] [mm] Pressure rating Threaded Hard rubber Polyurethane [bar] fasteners PN 40 4 × M 12 PN 40 4 × M 16 PN 40 4 ×...
  • Page 28 Installation Proline Promag 10 Nominal diameter EN (DIN) Max. tightening torque [Nm] [mm] Pressure rating Threaded Hard rubber Polyurethane [bar] fasteners 600 * PN 16 20 × M 33 PN 25 20 × M 36 PN 6 24 × M 24 PN 10 24 ×...
  • Page 29 Proline Promag 10 Installation Nominal ANSI Max. tightening torque diameter Hard rubber Polyurethane Pressure rating Threaded [mm] [inch] [lbs] fasteners [Nm] [lbf · ft] [Nm] [lbf · ft] 1 ½" Class 300 4 × ¾" 2" Class 150 4 × 5/8"...
  • Page 30 Installation Proline Promag 10 Nominal diameter Threaded Max. tightening torque [Nm] fasteners [mm] Pressure rating Hard rubber Polyurethane 12 × M 22 12 × M 24 16 × M 22 16 × M 24 Promag W tightening torques for AWWA...
  • Page 31 Proline Promag 10 Installation Nominal diameter AS 2129 Threaded Max. tightening torque [Nm] [mm] Pressure rating fasteners Hard rubber 1000 Table E 24 × M 30 1200 Table E 32 × M 30 Promag W tightening torques for AS 4087...
  • Page 32: Installing The Transmitter Housing

    Installation Proline Promag 10 Installing the transmitter housing 2.8.1 Turning the transmitter housing Turning the aluminum field housing Aluminum field housing for non-Ex area £ £ 180° 180° A0008982 2.8.2 Turning the onsite display Unscrew cover of the electronics compartment from the transmitter housing.
  • Page 33: Post-Installation Check

    Proline Promag 10 Installation " Caution! • The ambient temperature range (–20 to +60°C) may not be exceeded at the mounting location. Avoid direct sunlight. • If the device is mounted to a warm pipe, make sure that the housing temperature does not exceed +60 °C, which is the maximum permissible temperature.
  • Page 34: Wiring

    Wiring Proline Promag 10 Wiring Warning! Risk of electric shock! Components carry dangerous voltages. • Never mount or wire the measuring device while it is connected to the power supply. • Before connecting the power supply, check the safety equipment.
  • Page 35: Connecting The Various Housing Types

    Proline Promag 10 Wiring Connecting the various housing types Wire the unit using the terminal assignment diagram inside the cover. 3.1.1 Compact version Transmitter connection: Signal cable Power supply cable Electronics compartment cover (connection diagram on the cover of the connection compartment)
  • Page 36: Connecting The Remote Version Connecting Cable

    Wiring Proline Promag 10 Connecting the remote version connecting cable 3.2.1 Connecting cable for Promag E/L/P/W Connecting cable termination Terminate the signal and coil current cables as shown in the figure below (Detail A). Fit the fine-wire cores with cable end ferrules (Detail B).
  • Page 37 Proline Promag 10 Wiring 3.2.2 Promag H connecting cable Connecting cable termination Terminate the signal and coil current cables as shown in the figure below (Detail A). Fit the fine-wire cores with cable end ferrules (Detail B). Signal cable termination Make sure that the cable end ferrules do not touch the wire shields on the sensor side! Minimum distance = 1 mm (0.04 in), exception "GND"...
  • Page 38 Wiring Proline Promag 10 3.2.3 Connecting cable connection S1 E1 E2 S2GND E S n.c. n.c. n.c. n.c. n.c. n.c. E1 E2 GNDE A0008987 Transmitter housing on connection housing, remote version Sensor connection housing, remote version for Promag E/P/L/W Sensor connection housing, remote version for Promag H, DN 25 (1") Sensor connection housing, remote version for Promag H, DN 40 (1 ½")
  • Page 39: Potential Equalization

    Proline Promag 10 Wiring Potential equalization Perfect measurement is only ensured when the medium and the sensor have the same electrical potential. Most sensors have a reference electrode installed as standard, which guarantees the required potential connection. This usually means that the use of ground disks or other measures are unnecessary.
  • Page 40: Degree Of Protection

    Wiring Proline Promag 10 Degree of protection The devices meet all the requirements for IP 67. After mounting in the field or service work, the following points have to be observed to ensure that IP 67 protection is retained: • Install the measuring device in such a way that the cable entries do not point upwards.
  • Page 41: Commissioning

    Proline Promag 10 Commissioning Commissioning Switching on the measuring device On completion of the installation (successful post-installation check), wiring (successful post-connection check) and after making the necessary hardware settings, where applicable, the permitted power supply (see nameplate) can be switched on for the measuring device.
  • Page 42 Commissioning Proline Promag 10 4.2.3 Displaying error messages Type of error: P = Process error, S = System error XXXXXXXXXX Error message type: = Fault message, ! = Notice message #000 00:00:05 Error number Duration of the last error that occurred:...
  • Page 43: Navigating Within The Function Matrix

    Proline Promag 10 Commissioning Navigating within the function matrix > 3 s – – – – A0012683 Enter the function matrix (starting with measured value display) Select the group (e.g. OPERATION) Confirm selection Select function (e.g. LANGUAGE) Enter code 10 (only for the first time you access the function matrix) Confirm entry...
  • Page 44: Device Functions To Be Configured During Commissioning

    Commissioning Proline Promag 10 Device functions to be configured during commissioning Check the values and settings of the device functions not marked gray in the following function matrix (UNIT VOL. FLOW, UNIT VOLUME, LANGUAGE, CURRENT RANGE etc.) and adapt them to your application.
  • Page 45: Troubleshooting

    Proline Promag 10 Commissioning Troubleshooting A complete description of all the error messages is provided in the Operating Instructions on the CD-ROM. Note! The output signals (e.g. pulse, frequency) of the measuring device must correspond to the higher-order controller. Endress+Hauser...
  • Page 46 Commissioning Proline Promag 10 Endress+Hauser...
  • Page 47 Proline Promag 10 Commissioning Endress+Hauser...
  • Page 48 www.addresses.endress.com...

Table of Contents