Warnings for UL/cUL Marking
- Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
- The Inverter internal capacitor is still charged even after the power supply is turned OFF. To prevent
electrical shock, disconnect all power before servicing the Inverter. Then wait at least one minute
after the power supply is disconnected and all indicators are OFF.
- Do not perform a withstand voltage test on any part of the Inverter. This electronic equipment uses
semiconductors and is vulnerable to high voltage.
- Do not remove the Digital Operator or the blank cover unless the power supply is turned OFF. Never
touch the printed control board (PCB) while the power supply is turned ON.
- The Inverter is not suitable for use on a circuit capable of delivering more than 5,000 RMS symmetri-
cal amperes, 250 volts maximum (200-V-class Units) or 18,000 RMS symmetrical amperes, 480 V
maximum (400-V-class Units).
Separate motor overcurrent, overload and overheating protection is required to be provided in ac-
cordance with CANADIAN ELECTRICAL CODE, PART I and NEC.
Use 75°C copper wires or equivalent.
Low voltage wires shall be wired with Class I Wiring.
Une protection distincte contre les surintensités, la surcharge et la surchauffé de moteur doit être
fournie conformément
AU CODE CANADIEN DE L'ELECTRICITE, PREMIER PARTIE et LE NATIONAL DE L'ELECTRI-
CITE.
Checking Before Unpacking
3G3FV-A4037-CUE
Series
3G3FV Series
3G3HV Series
CAUTION
ATTENTION
Specifications
Blank
-E
-CE
-CUE
Maximum motor capacity
004
0.4 kW
007
0.75 kW
015
1.5 kW
022
2.2 kW
037
3.7 kW
Voltage class
B
4
Protective Structure
A
B
www.dadehpardazan.ir 88594014-15
Japanese model
English model
Conforms to EN Standards
Conforms to EN, UL/cUL Standards
055
5.5 kW
075
7.5 kW
110
11 kW
150
15 kW
185
18.5 kW
Single-phase, 200 VAC (200-V model)
Three-phase, 400 VAC (400-V model)
Panel-mounting (IP10 min.) or closed
wall-mounting models
Panel-mounting (IP00) models.
220
22 kW
300
30 kW
370
37 kW
450
45 kW
550
55 kW