Omron SYSDRIVE 3G3FV-*-CUE Installation Manual page 53

Table of Contents

Advertisement

Installation
H Wiring on the Output Side of Main Circuit
D Connecting the Terminal Block to the Load
Connect output terminals T1 (U), T2 (V), and T3 (W) to motor lead wires T1 (U), T2 (V), and T3 (W),
respectively. Check that the motor rotates forward with the forward command. Switch over any two of
the output terminals to each other and reconnect if the motor rotates in reverse with the forward com-
mand.
D Never Connect a Power Supply to Output Terminals
Never connect a power supply to output terminals T1 (U), T2 (V), and T3 (W). If voltage is applied to the
output terminals, the internal circuit of the Inverter will be damaged.
D Never Short or Ground Output Terminals
If the output terminals are touched with bare hands or the output wires come into contact with the Invert-
er casing, an electric shock or grounding will occur. This is extremely hazardous. Also, be careful not to
short the output wires.
D Do Not Use a Phase Advancing Capacitor or Noise Filter
Never to connect a phase advance capacitor or LC/RC noise filter to the output circuit. Doing so may
result in damage to the Inverter or cause other parts to burn.
D Do Not Use an Electromagnetic Switch or Magnetic Contactor
Do not connect an electromagnetic switch or magnetic contactor to the output circuit. If a load is con-
nected to the Inverter during running, an inrush current will actuate the overcurrent protective circuit in
the Inverter.
D Installing a Thermal Relay
This Inverter has an electronic thermal protection function to protect the motor from overheating. If,
however, more than one motor is operated with one Inverter or multi-polar motor is used, always install a
thermal relay (THR) between the Inverter and the motor and set n033 to 0 (no thermal protection).
In this case, program the sequence so that the magnetic contactor on the input side of the main circuit is
turned off by the contact of the thermal relay.
D Installing a Noise Filter on Output Side
Connect a noise filter to the output side of the Inverter to reduce radio noise and induction noise.
Power
supply
2-34
3G3FV
Signal line
Controller
www.dadehpardazan.ir 88594014-15
Noise filter
Induction
Radio noise
noise
AM radio
Chapter 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysdrive 3g3hv-*-cueSysdrive 3g3hv-*-cue-ce

Table of Contents