Rosemount 2088 and 2090
Changing a Transmitter
Address
Communicating with a
Multidropped
Transmitter
Polling a Multidropped
Loop
3-18
www.aotewell.com
To change the address of a multidropped transmitter, follow these fast key
sequences. To activate multidrop communication, the transmitter address
must be changed to a number from 1 to 15.
Field Communicator
1, 4, 3, 3, 1
4-20 mA Fast Keys
To communicate with a multidropped transmitter for the purpose of testing,
configuring, or formatting.
Field Communicator
1, 4, 3, 3, 2
4-20 mA Fast Keys
Polling a multidropped loop determines the model, address, and number of
transmitters on the given loop.
Field Communicator
Left Arrow, 4, 1, 1
4-20 mA Fast Keys