Detector Alarm

1. Indoor Unit Alarm
- If the concentration of the refrigerant in the air exceeds 6000 ppm, the indoor unit buzzer
goes off to alert the user.
* Release conditions: If the concentration of the refrigerant is 6000 ppm or less by ventilating
the immediate vicinity, or the power button of the wired remote control, wireless remote con-
trol, and central control is pressed.
2. Wired Remote Control
- If the concentration of the refrigerant in the air exceeds 6000 ppm, the error code CH230 is
displayed on the wired remote control.
* Disabling Conditions: Power to the indoor unit is cut off after 30 seconds.
3. Refrigerant Leak Detector
- Displays the state by using the LED of the indoor sensor of the refrigerant leak detector.
- If the concentration of the refrigerant in the air exceeds 6 000 ppm : The green and red LED
lights blink at the same time.
* Release condition: When the concentration of the refrigerant is 6000 ppm or less by ventilat-
ing the immediate vicinity.
- Normal mode: The green LED always turns on.
- Out of order: The green and red LED lights blink in turn.
* If the product is out of order, contact the service center to change the sensor.