How to Install

6. How to Install
1. Installation Place to Improve Detection Performance
- Installation Place by Refrigerant Characteristics
Because R410A is heavier than air, the refrigerant leak detector must be installed near the
floor.
Install at a height of 300-500 mm off the ground (generally lower than the height of a bed).
• When installed at a height of less than 300 mm, it can make faulty detections.
• If installed at a height greater than 500 mm, the detection performance deteriorates.
2. Securing the Installation Location
- Install with the appropriate connecting cable length to connect from the indoor unit.
- It must be installed properly to help facilitate servicing.
• Do not install a connecting cable that is 50 m or longer.
(It may cause communication failure.)
3. Installation Place to Prevent Wrong Detection
• Other Gas Factors
- Wrong alarm may go off due to gases other than R410A.
• Environmental Factors
- It must be installed away from a cold wind or a heat source like a radiator.
- Steam sources must be avoided.
- A humid environment or water prone areas must be avoided.
• False detection concerning the location
* Places where other gases may be generated: Fruit storage, closed space, and places where
exhaust gases are excessively emitted
* Places which are very humid or water prone: restroom, washstand