Test Run

8. Test Run

Pre-check

This is a step to check whether the refrigerant leak detector is properly installed for the test run.
1. Check whether the power is connected.
2. After connecting the power, 7 seconds is the initial sensor startup time.
3. After 7 seconds, ensure that the green LED light turns on.

Checking the refrigerant leak detector setting - Wired Remote Control

A function to set when a refrigerant leak detector is newly installed for an indoor unit, or the exist-
ing installation is removed.
Refrigerant Leak Detector
14
1. Press the function setting button for three seconds or
more to move to the remote control installer setting
mode.
- Press once shortly to move into the user setting mode.
It must be pressed for at least 3 seconds.
2. Press the function setting button repeatedly to move to
the menu for checking the setting of the refrigerant leak
detector as shown in the figure to the right.
3. Select functional code value 29 and
setting value 01 by using the
button.
When non-installation is set, if the refrigerant leaks, the
alarm of indoor unit buzzer and remote control does
not go off.
4. When the function selection ends, press the Set/Re-
lease button to complete the setting.
5. Press the Go Out button to move out from the setting
mode.
* If there is no button entry roughly for 25 seconds after
setting, automatically move out to the setting mode.
* If it is closed without pressing the Set button, the opera-
tional value is not set.