Carrier 070-08/024070 Installation, Start-Up, Operating And Service And Maintenance Instructions page 50

120/c series single-stage deluxe induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

blower motor BLWM will remain on lbr tile selected blower-
OFF delay period then switch to continuous-blower
speed.
When the R-to-W-and-Y/Y2,
R-to-W-and-Y/Y2-and-G,
R-to-
W-and-Yl-and-Y/Y2,
or
R-to-W-and-Yl-and-Y/Y2-and-G
circuits are energized tile furnace control CPU will switch to
or turn on the blower motor BLWM at HEAT speed, and
begin a beating cycle. The blower motor BLWM will remain
on until the end of the prepurge period, then shut o11"lot 24
seconds then come back on at HEAT speed. When the W input
signal disappears, the furnace control begins a normal inducer
post-purge period and the blower switches to COOL speed
afler a 3 second delay. If the R-to-W-and-Y/Y2-and-G
or
R-to-W-and-Yl-and-Y/Y2-and-G
signals
disappear
at the
same time, the blower l'flotor BLWM will remain on [_)r the
selected blower-OFF delay period. If the R-to-W-and-Y/Y2
or
R-to-W-and-Yl-and-Y/Y2
signals disappear, leaving the G
signal, the blower motor BLWM will remain on lot the
selected blower-OFF delay period then switch to continuous-
blower speed.
Step 4--Wiring
Diagrams
Relier to Fig. 56 lot wiring diagram.
Step
5--Troubleshooting
Relier to the service
label. (See Fig. 55
Service
Label.)
The
Troubleshooting
Guide
can
be
a useful
tool
in isolating
furnace
operation
problems.
Beginning
with
the
word
"StarL"
answer
each question
and flHlow the appropriate
arrow to the next
item.
The Guide
will help to identify
the problem
or failed component.
Alter replacing
any component,
verify correct
operation
sequence.
5O