General Venting Requirements; Masonry Chimney Requirements - Carrier 070-08/024070 Installation, Start-Up, Operating And Service And Maintenance Instructions

120/c series single-stage deluxe induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

CARBON MONOXIDE
POISONING
HAZARD
Failure to Ibllow the steps outlined below Ibr each appliance
connected to the venting system being placed into operation
could result in carbon monoxide poisoning or death.
The %llowing steps shall be lollowed lbr each appliance
connected to the venting system being placed into operation,
while all other appliances connected to the venting system are
not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system lor proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223. I/NFPA 54 or CSA B149.1, Natural Gas and
Prol)atle hlstallatio_l Code and these instructions.
Determine that there is no blockage or restriction, leakage,
corrosion
and other deficiencies,
which could cause an
unsale condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected
to the venting system are located and other
spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to
the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts_ so they are operating
at maximum speed. Do not operate a sunm_er exhaust fan.
6. Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so
appliance is operating continuously.
7. Test %r spillage fi'om draft hood equipped appliances at the
drali hood relief opening alter 5 ndnutes of main burner
operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above
tests, the venting system nmst be corrected in accordance
with the National Fuel Gas Code, ANSI Z223.1/NFPA .54
and/or (7\S_B149.1, Natutvd Gas and Propane Installation
Code.
9. After it has been determined that each appliance connected
to the venting
system
properly
vents when tested as
outlined
above_ return
doors_ windows,
exhaust
fans,
fireplace dampers and any other gas-fired burning
appliance to their previous conditions of use.
Vent
system
or vent
connectors
may
need
to be resized.
Vent
systems
or vent cormectors,
must be sized to approach
nlil'dlnum
size as determined
using appropriate
table
lbund
in the NFGC
or
NSCNGP1C.
GENERAL
VENTING
REQUIREMENTS
Follow
all salety
codes
%r proper
vent
sizing
and
installation
requirements,
including
local
building
codes,
the National
Fuel
Gas Code ANSI
Z223.1-2002/NFPA
.54-2002
(NFGC),
Parts
It)
and 13 in the United
States or the Natiomd
Stcm&_rd qf' Canada,
Narulvd
Gas
and
Propane
hlstalh_rion
Code
CSA-B149.1-011
(NSCNGPIC),
Section
7 and Appendix
C in Canada,
the
local
building
codes, and lhrnace
and vent manufacturers'
instructions.
These
lhrnaces
are design-certified
as Category
I furnaces
in
accordance
with
ANSI
Z21.47-2IIII3/CSA
2.3-211113 and operate
with a non-positive
vent static pmssurc
to minimize
the potential
lbr vent gas leakage.
Category
1 lhrnaces
operate
with a flue loss
not less than 17 percent
to minimize
the potential
lbr condensation
in the venting
system.
These furnaces
are approved
lot common
venting
and multistory
venting
with
other
fan assisted
or drali
hood equipped
appliances
in accordance
with the NFGC
or the
NSCNGPIC,
the
local
building
codes,
and
lurnace
and
vent
manufacturers'
instructions.
23
The lbllowing
inlormation
and warning nlust be considered
in
addition
to the requirements
defined
in the NFGC
and the
NSCNGP1C.
CARBON
MONOXIDE
POISONING
HAZARD
Faihn'e to %llow this warning could result in personal iniury
or death.
Do not bypass the draft salegnard
switch, as an unsali:
condition could exist which nmst be corrected.
1. If a vent (common or dedicated) becomes blocked, the fln'nace
will be shut off by the draft salbguard switch located on the
vent elbow.
2. Do not vent this Catego U I furnace
into a single-wall
dedicated or connnon vent. The dedicated or connnon vent is
considered to be the vertical portion of the vent system that
terminates outdoors.
3. Vent connectors
serving Category
1 furnaces
shall not be
connected
into any portion of a mechanical
drali system
operating under positive pressure.
4. In the U.S.: Do not vent this appliance with any solid fi_el
burning appliance.
In Canada: Check with the authority having jurisdiction
lbr
approval on use with solid lhel burning appliance.
5. Category
1 lhrnaces
nmst be vented
vertically
or nearly
vertically unless equipped with a listed power ventor.
6. Do not vent this appliance into an unlined masonry chimney.
Reli:r to Chinmey Inspection Chart, Fig. 32.
MASONRY CHIMNEY REQUIREMENTS
NOTE:
These furnaces
are CSA
design-certified
lbr use in
exterior tile-lined masonry
chinmeys with a factory accessory
Chinmey Adapter Kit. Reli:r to the furnace rating plate lk_rcorrect
kit usage. The Chimney Adapter Kits are lbr use with ONLY
furnaces having a Chimney Adapter Kit numbers marked on the
furnace rating plate.
If a clay tile-lined masonry chinmey is being used and it is exposed
to the outdoors below the roof line, relining ndght be required.
Chinmeys shall conlorm to the Standard %r Chinmeys, Fireplaces,
Vents, and Solid Fuel Burning Appliances ANSI/NFPA 211-2003
in the United States and to a Provincial or Territorial Building
Code in Canada (in its absence, the National Building Code of
Canada) and nmst be in good condition.
U.S.A.-Relbr
to Sections 13.1.9 and 13.2.20 of the NFGC or the
authority
having jurisdiction
to determine whether relining
is
required. If relining is required, use a properly sized listed metal
liner, Type-B vent, or a listed alternative venting design.
NOTE:
See the NFGC, 13.1.9 and 13.2.20 regarding alternative
venting design and the Exception, which cover installations such
as
the
Chimney
Adapter
Kits
KGACA02014FC
and
KGACA02015FC,
which are listed lbr use with these furnaces.
The Chinmey Adapter Kit is listed alternative venting system lbr
these lurnaces. See the kit instructions lbr complete details.

Advertisement

Table of Contents
loading

Table of Contents