Supply Air Temperature (Sat) Sensor; Outdoor Air Temperature (Oat) Sensor; Economi$Er2 - Carrier 50TC Series Installation Instruction

Single package rooftop cooling only with puron (r-410a) refrigerant sizes 08, 12, and 14 with novation coil sizes 08 - 14 with round tube/plate fin coil
Hide thumbs Also See for 50TC Series:
Table of Contents

Advertisement

BACnet OBJECT
POINT NAME
Space Temp / Zone Temp
Supply Air Temperature
Outside Air Temperature
Space Temperature Offset Pot
stpt_adj_offset
Safety Chain Feedback
safety_status
(1)
Compressor Safety Status
comp_status
Fire Shutdown Status
firedown_status
Enthalpy Status
enthalpy_status
Humidistat Input Status
humstat_status
Zone Temperature
Indoor Air CO2
Outdoor Air CO2
Space Relative Humidity
(2)
Supply Fan Status
(2)
Filter Status
(2)
Door Contact
door_contact_status
(2)
Remote Occupancy input
occ_contact_status
(2)
IGC input
igcovr_status
Economizer Output
econ_output
Supply Fan VFD
Supply Fan Relay
Cool 1 Relay State
Cool 2 Relay State
Cool 3 Relay State
Heat 1 Relay State
Heat 2 Relay State
Power Exhaust Relay State
Dehumidification Relay
LEGEND
AI
---
Analog Input
AO
---
Analog Output
BI
---
Binary Input
BO
---
Binary Output
(1)
Safety Chain Feedback: 24Vac required at this terminal to provide "Run Enable" status. See Input/Output section for additional instructions.
(2)
These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Section for wiring and setup instructions.
(3)
Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field installation.
(4)
Refer to the input configuration and accessory sections of the RTU Open Multi ---Protocol Controller Controls, Start ---Up, Operation and Troubleshooting manual for more detail.
The RTU Open controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP- - equipped 50TC unit, the unit is supplied with a
supply- - air temperature (SAT) sensor (33ZCSENSAT). This
sensor is a tubular probe type, approx 6- - inches (152 mm) in
length. It is a nominal 10- - k ohm thermistor.
The SAT is factory- - wired. The SAT probe is wire- - tied to
the supply- - air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re- - position the sensor in the flange of the supply- - air
opening or in the supply air duct (as required by local
1
codes). Drill or punch a
/
2
Use two field- - supplied, self- - drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 41.
Table 8 – RTU Open Controller Inputs and Outputs
TYPE OF I/O
NAME
DEDICATED INPUTS
zone_temp
AI (10K Thermistor)
sa_temp
AI (10K Thermistor)
oa_temp
AI (10K Thermistor)
AI (100K Potentiometer)
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
n/a
n/a
CONFIGURABLE INPUTS
iaq
AI (4--- 20 mA)
oaq
AI (4--- 20 mA)
space_rh
AI (4--- 20 mA)
sfan_status
BI (24 VAC)
filter_status
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
BI (24 VAC)
AO (4--- 20mA)
vfd_output
AO (2--- 10Vdc)
sfan
BO Relay (24VAC, 1A)
comp_1
BO Relay (24VAC, 1A)
comp_2
BO Relay (24VAC, 1A)
comp_3
BO Relay (24VAC, 1A)
heat_1
BO Relay (24VAC, 1A)
heat_2
BO Relay (24VAC, 1A)
pexh
BO Relay (24VAC, 1A)
dehum
BO Relay (24VAC, 1A)
- - in. hole in the flange or duct.
CONNECTION
CHANNEL DESIGNATION
PIN NUMBER(S)
J20--- 1 and 2
Analog Input 10
J2--- 1 and 2
Analog Input 6
J2--- 3 and 4
Analog Input 7
J20--- 3 and 4
Analog Input 11
J1--- 9
Binary Input 4
J1--- 2
Binary Input 3
J1--- 10
Binary Input 5
J2--- 6 and 7
Binary Input 8
J5--- 7 and 8
Binary Input 9
J13--- 1--- 4
Rnet
(4)
Analog Input 2
J4---2 and 3 or J4---5 and 6
Analog Input 1
Analog Input 10
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
J5---1 and 2 or J5---3 and 4,
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
(3)
J5---5 and 6 or J5---7 and 8
Binary Input 3, 5, 8, or 9, except where intrinsic input is used
Binary Input 9. Mandatory input on gas heat units.
OUTPUTS
J2--- 5
Analog Output 1
J22--- 1 and 2
Analog Output 2
J1--- 4
Binary Output 1 (G)
J1--- 8
Binary Output 5 (Y1)
J1--- 7
Binary Output 4 (Y2)
J11--- 5 and 6
Binary Output 7 (Y3)
J1--- 6
Binary Output 3 (W1)
J1--- 5
Binary Output 2 (W2)
J11--- 2 and 3 (N.O.)
Binary Output 8 (PE)
J11--- 7 and 8 (N.O.)
Binary Output 6
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory- - mounted in the EconoMi$er
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$er2 —
The RTU Open controller is used with EconoMi$er2
(factory- - installed option or field- - installed accessory) for
outdoor air management. The damper position is
controlled directly by the RTU Open controller; the
EconoMi$er2 unit has no internal logic device.
Outdoor air management functions can be enhanced with
field- - installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
sensor
2
Outdoor air CO
sensor
2
36
R
2 (FIOP