Supply Air Temperature (Sat) Sensor; Outdoor Air Temperature (Oat) Sensor; Economi$Er2; Field Connections - Carrier 50TC-A04 Installation Instructions Manual

50tc series single package rooftop cooling only
Hide thumbs Also See for 50TC-A04:
Table of Contents

Advertisement

Supply
Air Temperature
(SAT) Sensor
i
On FIOP-equipped
50TC unit, the unit is supplied with a
supply-air
temperature
(SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6-inches (152
mm) in length. It is a nominal 10-k ohm thermistor.
The SAT is factory-wired.
The SAT probe
is wire-tied
to
the supply-air
opening
(on the horizontal
opening
end) in
its shipping
position.
Remove
the sensor
for installation.
Re-position
the sensor
in the flange
of the supply-air
opening
or in the supply
air duct (as required
by local
codes).
Drill or punch
a 1/2-in. hole in the flange
or duct.
Use two field-supplied,
self-drilling
screws to secure
the
sensor probe in a horizontal
orientation.
See Fig. 40.
@
__
SUPPLYAIR
C08200
__ROOF
CURB
Fig. 40 - Typical Mounting
Location for Supply Air
Temperature
(SAT) Sensor on Small Rooftop Units
NOTE:
Refer
to
Form
33SC-68SI
for
complete
PremierLink
configuration,
operating
sequences
and
troubleshooting
information.
Have a copy
of this manual
available
at unit start-up.
NOTE:
The sensor
must
be mounted
in the discharge
airstream
downstream
of the cooling
coil and any heating
devices.
Be sure the probe
tip does not come
in contact
with any of the unit's heater
surfaces.
Outdoor
Air Temperature
(OAT) Sensor
i
The OAT is factory-mounted
in the EconoMi$er2
(FIOP
or accessory). It is a nominal 10k ohm thermistor attached
to an eyelet mounting ring.
EconoMi$er2
1
The
PremierLink
control
is
used
with
EconoMi$er2
(option
or accessory)
for outdoor
air management.
The
damper
position
is controlled
directly
by the PremierLink
control;
EconoMi$er2
has no internal
logic device.
Outdoor
air management
functions
can be enhanced
with
field-installation
of these accessory
control
devices:
Enthalpy
control
(outdoor
air or differential
sensors)
Space CO2 sensor
Outdoor
air CO2 sensor
Refer to Table 3 for accessory
part numbers.
Field
Connections
Field
connections
for accessory
sensor
and input devices
are made at the 16-pole
terminal
block (TB1)
located
on
the control
box bottom
shelf
in front
of the PremierLink
control
(See Fig. 38 or Fig. 39). Some
input devices
also
require
a 24-vac
signal
source;
connect
at CTB terminal
R at "THERMOSTAT"
connection
strip
for this
signal
source.
See connections
figures
on following
pages
for
field connection
locations
(and for continued
connections
at the PremierLink
board
inputs).
Table 4 provides
a summary
of field connections
for units
equipped
with Space Sensor. Table 5 provides
a summary
of
field connections
for units equipped
with Space Thermostat.
Table 3 - PremierLink
Sensor
Usage
OUTDOOR AIR
RETURN AIR
OUTDOOR AIR
RETURN AIR
APPLICATION
TEMPERATURE
TEMPERATURE
ENTHALPY SENSOR
ENTHALPY SENSOR
SENSOR
SENSOR
Differential Dry Bulb
Temperature with
PremierLink
(PremierLink requires
4- 20 mA Actuator)
Single Enthalpy with
PremierLink
(PremierLink requires
4- 20mA Actuator)
Differential Enthalpy
with PremierLink
(PremierLink requires
4- 20mA Actuator)
Included -
CRTEMPSNOO1AO0
Included -
Not Used
Included -
Not Used
Required -
33ZCT55SPT
or equivalent
Requires
-
33CSENTHSW
Requires -
33CSENTHSW
or equivalent
NOTES:
CO 2 Sensors (Optional):
33ZCSENC02
-
Room sensor (adjustable).
Aspirator box is required for duct mounting of the sensor.
33ZCASPC02
-
Aspirator box used for duct-mounted
CO 2 room sensor.
33ZCT55C02
-
Space temperature
and CO2 room sensor with override.
33ZCT56C02
-
Space temperature
and CO2 room sensor with override and setpoint.
Requires -
33CSENTSEN
or equivalent
24