Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb
and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional
dimensions are equal to or greater than the unit supply
duct opening dimensions for the first 18 in. (458 mm) of
duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
CAUTION
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage
to roofing materials.
Membrane roofs can be cut by sharp sheet metal
edges. Be careful when placing any sheet metal parts
on such roof.
UNIT
50TC ---A08
1290
50TC ---A09
1410
50TC ---A12
1515
50TC ---D/E08
1410
50TC ---D/E09
1525
50TC ---D/E12
1565
50TC ---D/E14
1720
NOTES:
1. Dimensions in ( ) are in millimeters.
2. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
3. Hook rigging shackles through holes in base rail, as shown in detail "A." Holes in base rails are centered around the unit center of gravity.
Use wooden top to prevent rigging straps from damaging unit.
MAX WEIGHT
LB
KG
IN
586
88.0
641
88.0
689
88.0
641
88.0
693
88.0
711
88.0
782
88.0
Fig. 7 - - Rigging Details
For Units with Accessory Electric Heaters —
All installations require a minimum clearance to
combustible surfaces of 1- - in (25 mm) from duct for first
12- - in (305 mm) away from unit.
Outlet grilles must not lie directly below unit discharge.
!
PERSONAL INJURY HAZARD
Failure to follow this warning could cause personal
injury.
For vertical supply and return units, tools or parts
could drop into ductwork and cause an injury. Install
a 90- - degree turn in the return ductwork between the
unit and the conditioned space. If a 90- - degree elbow
cannot be installed, then a grille of sufficient strength
and density should be installed to prevent objects
from falling into the
electric heater, supply duct will require 90- - degree
elbow.
DIMENSIONS
A
B
MM
IN
2235
40.0
2235
39.5
2235
41.0
2235
41.0
2235
40.5
2235
40.0
2235
28.5
11
WARNING
conditioned space. Due to
C
MM
IN
MM
1015
41.5
1055
1005
49.5
1255
1040
49.5
1255
1040
41.5
1055
1030
49.5
1255
1015
49.5
1255
725
53.0
1345
C06005

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents