Smoke Detector/Fire Shutdown (Fsd); Connecting Discrete Inputs - Carrier 50TC Series Installation Instruction

Single package rooftop cooling only with puron (r-410a) refrigerant sizes 08, 12, and 14 with novation coil sizes 08 - 14 with round tube/plate fin coil
Hide thumbs Also See for 50TC Series:
Table of Contents

Advertisement

J4-1 or J4-4 + 24 VDC Supply Voltage
J4-2 or J4-5 (-)4 to 20 mA Current Loop Output
to RTU Open controller
Humidistat: The accessory humidistat provides the RTU
Open controller insight to the relative humidity in the
space. The humidistat reads the RH level in the space and
compares it to its setpoint to operate a dry contact. The
humidistat is a dedicated input on the configurable input 9
and tells the RTU Open controller when the RH level is
HIGH or LOW. The normal condition for humidity is
LOW. A normally open humidistat is the factory default
control for the Humidi- - MiZer
To wire in the field:
S J5- - 8 = 24 VAC source for dry contact
S J5- - 7 = Signal input
Smoke Detector/Fire Shutdown (FSD) —
On 50TC units equipped with factory- - installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit's CTB input. The FSD function is initiated via the
smoke detector's Alarm NO contact set. The RTU Open
controller communicates the smoke detector's tripped
status to the BAS building control. See Fig. 59 and 60
(RTU Open Controller wiring schematics).
The
Fire
Shutdown
MENU
Config
Inputs
input 5, identifies the normally
open status of this input when there is no fire alarm.
Connecting Discrete Inputs —
Filter
Status:
The
filter
field- - installed accessory. This accessory detects plugged
filters. When installing this accessory, the unit must be
configured
for
filter
MENU
Config
Inputs
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 58 and Fig. 59 or 60 for wire terminations at J5.
Fig. 67 - - Duct Relative Humidity Sensor Typical Wiring
R
system option.
Switch
configuration,
status
accessory
is
status
by
setting
input 3, 5, 8, or 9 to Filter
SPAN
ZERO
4-20
VAC
GND 0-5V
mA
or
or
VDC
0-10V
Fan Status: The fan status accessory is a field- - installed
accessory. This accessory detects when the indoor fan is
blowing air. When installing this accessory, the unit must
be
configured
MENU
Config
Inputs
Status and normally open (N/O) or normally closed (N/C).
Input 8 or 9 is recommended for easy of installation. Refer
to Fig. 58 and Fig. 59 or 60 for wire terminations at J5.
Remote Occupancy: The remote occupancy accessory is
a field- - installed accessory. This accessory overrides the
unoccupied mode and puts the unit in occupied mode.
When installing this accessory, the unit must be
configured
for
MENU
Config
Inputs
Occupancy and normally open (N/O) or normally closed
(N/C).
Also set MENU
on/off. Input 8 or 9 is recommended for ease of installation.
Refer to Fig. 58 and Fig. 59 for wire terminations at J5.
Power Exhaust (output): The relay used by the RTU
Open controller board to control power exhaust is a dry
contact which means it does not have 24vac. This 24vac
must be connected to the relay to allow it to operate the
power exhaust relay in the PE accessory. A 24vac source
must be provided to J11- - 2 on the RTU Open controller
board. This can be provided by the unit's transformer from
various sources. The "R" terminal on the unit's low
voltage terminal board (LVTB) is a logical source. Refer
a
to Fig. 58 and Fig. 59 or 60 for wire terminations at J11.
39
Relative Humidity Sensor
(Polarized Male Connector)
for
fan
status
by
input 3, 5, 8, or 9 to Fan
remote
occupancy
by
input 3, 5, 8, or 9 to Remote
Schedules
occupancy source to DI
C12756
setting
setting