FREEZE CYCLE DISCHARGE PRESSURE
HIGH CHECKLIST
Improper Installation
•
Refer to "Installation/Visual Inspection Checklist"
(page 108)
Air Condenser
•
Dirty condenser filter
•
Dirty condenser fins
•
High inlet air temperature (Self contained 110°F/
43°C max. Remote 120°F/49°C max.).
•
Condenser discharge air recirculation
•
Defective fan cycling control (page 167)
•
Defective fan motor
•
Defective head pressure control valve {Remotes}
(page 164)
Water Condenser
•
Low water pressure [20 psig (138 kPa) min.]
•
High inlet water temperature (90°F/32°C max.)
•
Dirty condenser
•
Dirty/Defective water regulating valve
•
Water regulating valve out of adjustment
Other
•
Overcharged
•
Non-condensable (air) in system
•
Wrong type of refrigerant
•
Non-Manitowoc components in system
•
High side refrigerant lines/component restricted