Freeze Cycle Discharge Pressure High Checklist; Improper Installation; Water Condenser - Manitowoc S300 Technician's Handbook

S series
Table of Contents

Advertisement

FREEZE CYCLE DISCHARGE PRESSURE
HIGH CHECKLIST

Improper Installation

Refer to "Installation/Visual Inspection Checklist"
(page 108)
Air Condenser
Dirty condenser filter
Dirty condenser fins
High inlet air temperature (Self contained 110°F/
43°C max. Remote 120°F/49°C max.).
Condenser discharge air recirculation
Defective fan cycling control (page 167)
Defective fan motor
Defective head pressure control valve {Remotes}
(page 164)

Water Condenser

Low water pressure [20 psig (138 kPa) min.]
High inlet water temperature (90°F/32°C max.)
Dirty condenser
Dirty/Defective water regulating valve
Water regulating valve out of adjustment
Other
Overcharged
Non-condensable (air) in system
Wrong type of refrigerant
Non-Manitowoc components in system
High side refrigerant lines/component restricted
Part Number 80-1479-3 7/10