CALCULATING REMOTE CONDENSER

INSTALLATION DISTANCES

Manitowoc warrants only complete new and
NOTE:
unused remote packages. Warranty on the
refrigeration system will be void if a new ice machine
head section is connected to existing (used) tubing or
condensers.

Line Set Length

The maximum length is 100' (30.5 m).
The ice machine compressor must have the proper oil
return. The receiver is designed to hold a charge
sufficient to operate the ice machine in ambient
temperatures between -20°F (-28.9°C) and 120°F
(49°C), with line set lengths of up to 100' (30.5 m).

Line Set Rise/Drop

The maximum rise is 35' (10.7 m).
The maximum drop is 15' (4.5 m).
If a li ne se t h as a rise fo llowed by a drop , a nother
rise cann ot be mad e. Likew ise, if a li ne se t h as a
drop fo llowed by a rise,
made.
Part Number 80-1479-3 7/10