Refrigerant Recovery/Evacuation

NORMAL SELF-CONTAINED MODEL
PROCEDURES
Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturer's recommendations.
Manitowoc assumes no responsibility for the use o f
contaminated refrigerant. Damage resulting from the
use of cont
aminated refri gerant i s the so le
responsibility of the servicing company.
Replace the l iquid li ne d rier be fore evacu ating a nd
recharging. Use only a Manitowoc (OEM) liquid line
filter-drier to prevent voiding the warranty.

Connections

Manifold gauge sets must utilize low loss fittings to
comply with U.S. Government rules and regulations.
Make these connections:
Suction side of the compressor through the suction
service valve.
Discharge side of the compressor through the
discharge service valve.
Part Number 80-1479-3 7/10