Chapter 2
Installing the Device
The following shows the proper relay connections.
Figure 4: Failsafe Alarm Relay Wiring
1. Normally Closed    2. Common    3. Normally Open
Section 2.7

Connecting Power

The RUGGEDCOM RS910L supports power input from a single high AC/DC or low DC power supply.
IMPORTANT!
• For 110/230 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
• For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
• Use only #16 gage copper wiring when connecting terminal blocks.
• Equipment must be installed according to applicable local wiring codes and standards.
• All line-to-ground transient energy is shunted to the Surge Ground terminal. In cases where users
require the inputs to be isolated from ground, remove the ground braid between Surge and Chassis
Ground. Note that all line-to-ground transient protection circuitry will be disabled.
CONTENTS
Section 2.7.1, "Connecting High AC/DC Power"
Section 2.7.2, "Connecting Low DC Power"
Section 2.7.1
Connecting High AC/DC Power
To connect a high AC/DC power supply to the device, do the following:
CAUTION!
Electrical hazard – risk of damage to equipment. Do not connect AC power cables to terminals for DC
power. Damage to the power supply may occur.
10
1
2
3
RUGGEDCOM RS910L
Installation Guide
Connecting Power