11 UL Standards

11
UL Standards
Precautions for UL/cUL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product
testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to
receive UL certification, all components inside that product must also receive UL certification.
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued
compliance when using this drive in combination with other equipment, meet the following conditions:
Installation Area
Do not install the drive to an area greater than pollution severity degree 2 (UL standard).
Ambient Temperature
IP20 enclosure: -10 to +50C
Main Circuit Terminal Wiring
YASKAWA recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of
UL Listed closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-L20085 to
20415 and 40045 to 40216. Use only the tools recommended by the terminal manufacturer for crimping.
The wire gauges listed in the tables below are YASKAWA recommendations. Refer to local codes for proper wire gauge
selections.
Note:
The mark
indicates the terminals for protective ground connection. (as defined in IEC/EN 60417-5019)
Grounding impedance;
200 V: 100  or less
400 V: 10  or less
Three-Phase 200 V Class
For Europe and China
Model
Recommended
Terminal
CIMR-L
R/L1, S/L2,
T/L3
U/T1, V/T2,
20008
W/T3
<4>
–, +1, +2
B1, B2
R/L1, S/L2,
T/L3
U/T1, V/T2,
20011
W/T3
<4>
–, +1, +2
B1, B2
EN 52
<1>
Applicable
Recommended
Gauge
Gauge
mm
mm
2
2
2.5
2.5 to 6
2.5
2.5 to 6
2.5 to 6
2.5 to 6
2.5
2.5 to 6
2.5
2.5 to 6
2.5
2.5 to 6
2.5 to 6
2.5 to 6
2.5
2.5 to 6
For Asia
<2>
Applicable
Recommended
Gauge
Gauge
mm
mm
2
2
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
2
2 to 5.5
3.5
2 to 5.5
YASKAWA ELECTRIC TOEP C710616 33G AC Drive L1000A - Quick Start Guide
For U.S.A
<3>
Applicable
Gauge
Gauge
AWG, kcmil
AWG, kcmil
14
14 to 10
14
14 to 10
14 to 10
14 to 10
10
14 to 10
12
14 to 10
14
14 to 10
14 to 10
14 to 10
10
14 to 10
Tightening
Screw
Torque
Size
Nm (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)