Setup and Adjustments

Port A has the flow characterizing disk. Connect Port A
to the outlet from the coil. On three-way models, use
Port B as the bypass port.
Two-way VG1000 Series Ball Valves are fully open
when the electric actuator is fully counterclockwise
(CCW) and fully closed when the electric actuator is
fully clockwise (CW).
For three-way valves, the Coil Port A and Common
Port AB are fully open when the electric actuator is fully
CCW, as shown in Figure 11. The Bypass Port B and
Common Port AB are fully open when the actuator is
fully CW, as shown in Figure 12.
Figure 11: VG18A5 Series Three-Way Ball Valve
(Coil Port A Open to Common Port AB)
Port A
Coil
Port B Bypass
Figure 12: VG18A5 Series Three-Way Ball Valve
(Bypass Port B Open to Common Port AB)
Port A
Coil
Port B Bypass
For non-spring return and spring-to-open proportional
control models in the Direct Acting (DA) mode, a
minimum control signal drives the electric actuator to
the fully CCW position while a maximum control signal
drives the electric actuator in the fully CW position.
Port AB
Common
Port AB
Common
VG1000 Series Flanged Ball Valves Installation Instructions
For spring-to-close proportional control models in the
DA mode, a minimum control signal drives the electric
actuator to the fully CW position, while a maximum
control signal drives the electric actuator to the fully
CCW position.

Troubleshooting

Servicing the Actuator or Piping System

When servicing the electric actuator or the piping
system:
disconnect the power supply to the actuator
WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies
!
before making electrical connections. More
than one disconnection or isolation may be
required to completely de-energize
equipment. Contact with components
carrying hazardous voltage can cause
electric shock and may result in severe
personal injury or death.
AVERTISSEMENT : Risque de décharge
électrique.
Débrancher ou isoler toute alimentation
avant de réaliser un raccordement
électrique. Plusieurs isolations et
débranchements sont peut-être nécessaires
pour -couper entièrement l'alimentation de
l'équipement. Tout contact avec des
composants porteurs de tensions
dangereuses risque d'entraîner une
décharge électrique et de provoquer des
blessures graves, voire mortelles.
relieve the pressure in the piping system
CAUTION: Risk of Property Damage.
Do not apply power to the system before
!
checking all wiring connections. Short
circuited or improperly connected wires may
result in permanent damage to the
equipment.
MISE EN GARDE : Risque de dégâts
matériels.
Ne pas mettre le système sous tension
avant d'avoir vérifié tous les raccords de
câblage. Des fils formant un court-circuit ou
connectés de façon incorrecte risquent
d'endommager irrémédiablement
l'équipement.
7

Advertisement

Table of Contents
loading

Table of Contents