Setup And Adjustments - Johnson Controls IOM3711 Installation Manual

Input/output module
Hide thumbs Also See for IOM3711:
Table of Contents

Advertisement

Table 5: Termination Details
Type of Field Device
4–20 mA Output to Actuator
Analog Output (Current)
4–20 mA Output to Actuator

Setup and Adjustments

Setting the device addresses
Metasys field expansion modules are master devices on
MS/TP (SA or FC) buses. Before operating expansion
modules on a bus, you must set a valid and unique device
address for each expansion module on the bus. You
set a expansion module's device address by setting the
positions of the switches on the DIP switch block at the
top of the expansion module (Figure 1). Device addresses
4 through 127 are the valid addresses for these expansion
modules.
The DIP switch block has eight switches numbered 128,
64, 32, 16, 8, 4, 2, and 1 (Figure 9). Switches 64 through 1
are device address switches. Switch 128 is a mode switch
that enables a expansion module to operate on a ZFR/ZFR
Pro Series Wireless Field Bus. Switch 128 must be set to off
for all hard-wired SA and FC bus applications. Set switch
128 to ON for wireless FC bus applications only.
14
IOM3711 Input/Output Module Installation Guide
Type of Input/
Termination diagrams
Output
UO
UO
UO
Figure 9: Device address DIP switch block set to
address 21
Note: Expansion module ships with switch 128 ON
and the remaining address switches off rendering
the expansion modules wired devices, which do not
operate on MS/TP buses, but will not interfere with
bus operation. Set a valid and unique device address
on the expansion module before applying power to
the expansion module on the bus.
To set the device addresses on Metasys field
expansion modules:
1.
Set all of the switches on the address DIP switch
block (128 through 1) to off.