Repair Information; Technical Specifications; Vg1000 Series Flanged Ball Valves - Johnson Controls VG1xA5Gx Installation Instructions Manual

Vg1000 series vg12a5 series vg18a5 series flanged ball valves
Table of Contents

Advertisement

Repair Information

If the VG1000 Series Flanged Ball Valve fails to
operate within its specifications, replace the unit. For a
replacement valve, contact the nearest
Johnson Controls® representative.

Technical Specifications

VG1000 Series Flanged Ball Valves

1
Service
Valve Fluid Temperature Limits
Valve Body Pressure/
Temperature Rating
Maximum Closeoff Pressure
Maximum Recommended Operating Pressure
Drop
Flow Characteristics
2
Rangeability
Leakage
End Connections
Minimum Ambient Operating
Temperature
Maximum Ambient
3
Operating Temperature
Materials
Compliance
1.
Refer to VDI 2035 Guideline for proper water treatment.
2.
Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
3.
In steam applications, install the valve with the stem horizontal to the piping, and wrap the valve and piping with insulation.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Water
Steam
Two-Way
Three-Way
Two-Way
Three-Way
Two- or Three-Way
Three-Way
-4°F (-20°C)
-40°F (-40°C)
122°F (50°C)
131°F (55°C)
Body
Flanges
Ball
Stem
Europe
VG1000 Series Flanged Ball Valves Installation Instructions
Hot water, chilled water, 50/50 Glycol solutions, and 25 psig
(172 kPa) saturated steam for HVAC systems
0 to 284°F (-18 to 140°C)
ASME Class 150
250 psi at -20 to 100°F (-29 to 38°C)
235 psi at: 200°F (93°C)
218 psi at: 284°F (140°C)
25 psig (172 kPa) saturated steam for HVAC systems
100 psi (689 kPa)
50 psi (345 kPa)
30 psi (207 kPa) for quiet service
Equal Percentage
Equal Percentage Flow Characteristics of In-line Port or
Linear Percentage Flow Characteristics of Angle Port
Greater than 500:1
0.01% of maximum flow, control port, ANSI/FCI 70-2, Class 4
1% of maximum flow, bypass port
ASME Class 150 Flange
M9124 Series Non-Spring Return Actuators
M9220 Series Spring Return Actuators
M9124 Series Non-Spring Return Actuators
M9220 Series Spring Return Actuators
Brass
Ductile Iron
300 Series Stainless Steel
300 Series Stainless Steel
CE Mark - Johnson Controls, Inc. declares that this product is in
compliance with the essential requirements and other relevant
provisions of the Pressure Equipment Directive (PED).