Down Draughts; Ventilation And Combustion Air Regulations - Stanley Cara Plus Installation And Operating Instructions Manual

Solid fuel high output boiler insert stove
Table of Contents

Advertisement

DOWN DRAUGHTS

However well designed constructed and positioned,
the satisfactory performance of the flue can be
adversely affected by down draught caused by near-
by hills, adjacent tall buildings or trees. These can
deflect wind to blow directly down the flue or create
a zone of low pressure over the terminal.
A suitable terminal or cowl will usually effectively
combat direct down blow but no cowl is likely to pre-
vent down draught due to a low pressure zone.
(See Fig.11).
Fig 11
Direction of wind
Pressure zone
Direction of wind
Pressure zone
Direction of wind
Pressure zone
Suction zone
Suction zone
10
VENTILATION & COMBUSTION AIR REQUIRE-
MENTS
It is imperative that there is sufficient air supply to
the stove in order to support correct combustion.
The air supply to this appliance must comply with
current Building Regulations Part J, Heat Providing
Appliances. If another appliance is fitted in an adja-
cent room it will be necessary to calculate an addi-
tional air supply.
The minimum effective air requirement for this appli-
2
ance is 66cm
. When calculating combustion air
requirements for this appliance use the following
2
equation: 550mm
per each kW of rated output
above 5 kW should be
draught stabiliser is used the total free area shall be
2
increased by 300mm
If there is another appliance using air fitted in the
same or adjacent room, it will be necessary to pro-
vide an additional air supply.
Note:
There must not be an extractor fan fitted in the same
room as the stove as this can cause the stove to
emit smoke and fumes into the room.
All materials used in the manufacture of air vents
should be such that the vent is dimensionally stable,
corrosion resistant, and no provision for closure.
The effective free area of any vent should be ascer-
tained before installation. The effect of any grills
should be allowed for when determining the effective
free area of any vent.
Air vents should be positioned so that they are not
liable to blockage.
Air vents direct to the outside of the building should
be located so that any air current produced will not
pass through normally occupied areas of the room.
An air vent outside the building should not be locat-
ed less than the dimensions specified within the
Building Regulations and B.S. 8303: Part 1 from any
part of any flue terminal. These air vents must also
be satisfactorily fire proofed as per Building
Regulations and B.S. 8303: Part 1.
Air vents in internal walls should not communicate
with bedrooms, bedsits, toilets, bathrooms or rooms
containing a shower.
Air vents traversing cavity walls should include a
continuous duct across the cavity. The duct should
be installed in such a manner as not to impair the
weather resistance of the cavity.
provided, where a flue
for each kW of rated output.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents