Service and Troubleshooting
November 2017
Figure 7-6. Suppression of False Echoes
B
A.
Amplitude threshold
B.
Disturbing object
C.
False echo suppression
D.
Suppressed echo
E.
Surface
Prerequisites
Follow these recommendations before suppressing new false echoes:
Make sure a correct amplitude threshold is set (see
Make sure the level is stable. A fluctuating level may indicate a temporary disturbance which is not due
to an interfering object.
Only suppress echoes which can be clearly identified as objects in the tank. Compare the list of
interfering echoes with the tank drawing or visual inspection of the tank.
Do not suppress false echoes located below the product surface.
Keep the number of suppressed false echoes to a minimum.
It may be necessary to suppress new false echoes at a later stage when objects have become visible due
to surface movement.
Procedure
Rosemount Radar Master Plus
To add a new false echo suppression:
1. Under Service Tools, select Echo Curve.
2. In the echo curve, click
98
A
C
D
E
0
1 000
2 000
3 000
4 000
at the unknown echo peak, and then select Suppress.
meter
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
5 000
6 000
7 000
mV
"Set amplitude thresholds" on page
Reference Manual
00809-0100-4408, Rev BA
96).
Service and Troubleshooting