Samsung AC071MN4PKH Installation Manual page 14

Ac***mn4pkh series
Hide thumbs Also See for AC071MN4PKH:
Table of Contents

Advertisement

Installation Procedure
5 Push the drain hose up to insulation when connecting
the drain hose to drain socket.
Metal clamp
Large seailng pad
Drain hose
CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
Install air ventilation to drain condensation smoothly.
14
English
Drain socket
Drain hose
Drain pipe
Be sure to bond the drain
hose and the main pipe.
PVC Tube Joint
+ VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
Air ventilation
Ceiling
If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than
550 mm, there may be water leaks.
Band joint
Do not give the hose an upward gradient beyond
the connection port. This will cause water to flow
backwards when the unit is stopped, resulting in
water leaks.
Under gradient
Do not apply force to the piping on the unit side
when connecting the drain hose. The hose should not
be allowed to hang loose from its connection to the
unit. Fasten the hose to a wall, frame or other support
as close to the unit as possible.
Support pieces
300 mm
or less
20 mm or more
Drain hose
Ceiling
Ceiling
1 to 1.5 m
1/100 or more
Ceiling

Hide quick links: