Samson 5824 Mounting And Operating Instructions page 50

Electric actuators, with / without fail-safe action, version with positioner
Table of Contents

Advertisement

Configuration and operation using TROVIS-VIEW
Stroking speed
The actuator stem moves to the position determined by the input signal at the selected strok-
ing speed. There are three speed levels:
− Slow
= 0.135 mm/s
− Standard = 0.197 mm/s
− Fast
= 0.365 mm/s
Speed level settings: Settings\Actuator\Travel
Function
Speed level
Note
The transit time is calculated from the travel and the stroking speed. The transit time is the
time that the actuator stem needs to move through the adjusted travel.
The following applies:
Dead band (switching range)
The dead band determines how sensitive the actuator reacts. A change in the input signal by
the hysteresis first causes a minimally small change in the valve position.
Dead band settings: Settings\Actuator\Travel
Function
Dead band (switching range)
50
Transit time [s]
=
WE
Adjustment range
Standard
Slow, Standard, Fast
Travel [mm]
Stroking speed [mm/s]
WE
Adjustment range
2.0 %
0.5 to 5.0 %