Samson 5824 Mounting And Operating Instructions page 47

Electric actuators, with / without fail-safe action, version with positioner
Table of Contents

Advertisement

End position guiding
The actuator stem moves to the end position earlier if the end position guiding function is ac-
tive.
− End position guiding (stem extends)
The actuator stem moves the valve to the closed position when the input signal reaches
the value End position guiding (stem extends).
− End position guiding (stem retracts)
The actuator stem moves the valve to the fully open position when the input signal reach-
es the value End position guiding (stem retracts).
Note
When 'End position guiding (stem extends)' = 0 % and 'End position guiding (stem retracts)'
= 100 %, the end positioning guiding function is deactivated.
End position guiding settings: Settings\Actuator\Functions
Functions
End position guiding (stem extends)
End position guiding (stem retracts)
EB 5824-2 EN
Configuration and operation using TROVIS-VIEW
WE
1.0 %
97.0 %
Adjustment range
0.0 to 49.9 %
50.0 to 100.0 %
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5825

Table of Contents