Installing Sensors

4-1-4 Connecting Sensors

4-2

Installing Sensors

4-2-1 Installation Method

V600-HS51
Mounting to Brackets: Mounting Hole Dimensions
44
Hold the black part A of the connector, align the notch on the connector with the
notch in the jack, and insert the connector until it snaps in.
To disconnect the Sensor, pull portion B of the connector.
Note
1. When inserting the connector, always hold the molded section A. Pressing
part B will not lock the connector.
2. When disconnecting the connector, always hold part B and then pull it out.
The V600-HS51 Sensor is M12 in size. When embedding or attaching to metal,
separate the communications section (coil tip) from the metal by at least 15 mm
in all directions.
Note Do not let the surrounding metal extend beyond the end of the Sensor.
Part B
Part A
Surrounding metal
30 ( 15)-mm dia. min.
Sensor
7 mm min.
+0.5
12
mm dia.
0
Section
4-2
Amplifier