Parameters/address space
4.1 Parameters
Parameter
Reaction to CPU STOP •
Potential group
Only when configuring using a PROFIBUS GSD file; does not apply to configuration with STEP 7 via HSP. The parame-
1
ter assignment options are limited because PROFIBUS GSD configuration limits the number of parameters to a maxi-
mum of 244 bytes for each ET 200SP station. If required, you can still assign these parameters using the data record
128 as described in the column "GSD file PROFINET IO" (see table above). The parameter length of the I/O module is 8
bytes.
16
Value range
Turn off
Keep last value
Output substitute value 1
Use potential group of the
left module (module
plugged into a dark-
colored BaseUnit)
Enable new potential
group (module plugged in-
to light-colored BaseUnit)
Default
Reconfig-
uration in
RUN
Turn off
Yes
Use potential
No
group of the left
module
Digital output module RQ 4x24VUC/2A CO ST (6ES7132-6GD51-0BA0)
Scope with configuration software,
e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Module
Module
Module
Manual, 09/2017, A5E32855952-AB