WARNING
Improper Unit Lift!
Do not lift the unit from top! Lift from
lifting lugs only located at bottom of
unit. Test lift unit approximately 24
inches to verify proper center of
gravity lift point. To avoid dropping
of unit, reposition lifting point if unit
is not level. Failure to properly lift
unit could result in death or serious
injury or possible equipment or
property-only damage.
WARNING
Heavy Objects!
Follow good lifting practices before
lifting the unit, such as estimating
center of gravity and test lifting the
unit to check for balance and
stability. Each of the cables (chains
or slings) used to lift the unit must be
capable of supporting the entire
weight of the unit. Lifting cables
(chains or slings) may not be of the
same length. Adjust as necessary for
even unit lift. Other lifting
arrangements could cause
equipment or property-only damage.
Failure to properly lift unit could
result in death or serious injury.
6

Installation

Service Clearance

Recommendations
For unit sizes 3 to 8, locate the
module to allow removal of the
energy wheel cassette through the
access panel. Typically, the minimum
clearance is equal to the module
width plus 12 inches.
For unit sizes 10 to 50, locate the
module to allow all access doors to
open fully. Make provisions for
temporary access on either side of
the module for complete removal of
the cassette/wheel frame. This would
be required if complete replacement
of the entire cassette/wheel
assembly were needed. The
minimum recommended clearance
for this is equal to the module width
plus 12 inches.
Local electrical code clearance
requirements must be considered
when a factory-installed starter is
provided.
.
Figure 3. Use all lifting lugs when suspending energy wheel modules

Rigging/Lifting

Refer to the M-Series air handler
installation and maintenance
manual, CLCH-SVX03B-EN, for
instructions on equipment rigging
and lifting. This manual ships inside
the air handler fan module.
Module Weights and
Dimensions
Refer to Trane catalog CLCH-PRC006-
EN or equipment submittals for
module weights and dimensions.
Suspending Modules with
Base Rails
When suspending an energy wheel
module, it is required to suspend it
from all lifting lungs on both the
energy wheel module and any
adjoining modules (see Figure 3).
CLCH-SVX02C-EN