AAON RN SERIES Installation Operation & Maintenance page 11

Horizontal packaged rooftop units, heat pumps, & outdoor air handling units
Table of Contents

Advertisement

WARNING
Always use a pressure regulator,
valves
and
gauges
incoming pressures when pressure
testing a system. Excessive pressure
may cause line ruptures, equipment
damage or an explosion which may
result in injury or death.
CAUTION
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not
use
alkaline
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
WARNING
Some
chemical
compounds are caustic or toxic. Use
these substances only in accordance
with
the
manufacturer's
instructions.
Failure
instructions may result in equipment
damage, injury or death.
CAUTION
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
to
control
chemical
coil
coil
cleaning
usage
to
follow
CAUTION
Door
compartments
hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.
CAUTION
Cleaning
the
cooling
condenser water loop with harsh
chemicals such as hydrochloric acid
(muriatic acid), chlorine or other
chlorides,
can
refrigerant-to-water heat exchanger.
Care should be taken to avoid
allowing chemicals to enter the
refrigerant-to-water heat exchanger.
See Appendix A - Heat Exchanger
Corrosion
Resistance
information.
WARNING
OPEN LOOP APPLICATIONS
Failure of the condenser as a result
of chemical corrosion is excluded
from coverage under AAON Inc.
warranties and the heat exchanger
manufacturer's warranties.
containing
tower
or
damage
the
for
more
11