Horizontal water-source heat pump units (48 pages)
Summary of Contents for AAON CB-024
Page 1
CB SERIES Condensing Units Installation, Operation & Maintenance WARNING WARNING QUALIFIED INSTALLER FOR YOUR SAFETY Improper installation, adjustment, Do not store or use gasoline or other alteration, service or maintenance flammable vapors and liquids in the cause property damage, vicinity of this or any other appliance. personal injury or loss of life.
Table of Contents ® AAON CB Series Features and Options Introduction ..............5 Safety .............................. 6 CB Base Model and Features Description ..................10 General Description ........................11 Codes and Ordinances ......................11 Receiving Unit .......................... 11 Storage ............................12 Direct Expansion (DX) Condensing Units ................
Page 3
Compressor Lockouts ....................... 36 Maintenance ..........................37 Coils ............................37 E-Coated Coil Cleaning ......................37 DX Cooling ..........................39 Condenser Fan Motor ....................... 39 Replacement Parts ........................39 Warranty, Service, and Parts Department ................. 39 Refrigerant Piping Diagrams ......................40 CB Series Startup Form ........................
Page 4
Index of Tables and Figures Tables: Table 1 - Recommended Elevation Minimums ................15 Table 2 - Predetermined Line sizes for CB units with two step compressors and R-410A ..25 Table 3 - Acceptable Refrigeration Circuit Values ............... 28 Table 4 - Performance Testing Air Flow Setpoints ..............
® AAON CB Series Features and Options Introduction Energy Efficiency System Integration Two Step or Variable Capacity Scroll Split System Matching Compressor Modulating Head Pressure Control Air-Source Heat Pump Single Point Power Variable Speed Condenser Fans for Head ...
Safety Attention should be paid to the following statements: NOTE - Notes are intended to clarify the unit installation, operation and maintenance. CAUTION - Caution statements are given to prevent actions that may result in equipment damage, property damage, or personal injury. WARNING - Warning statements are given to prevent actions that could result in equipment damage, property damage, personal injury or death.
Page 7
WARNING WARNING GROUNDING REQUIRED FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD All field installed wiring must be Failure to replace proper controls completed by qualified personnel. Field installed wiring must comply could result in fire, explosion or with NEC/CEC, local state carbon monoxide poisoning.
Page 8
WARNING CAUTION UNIT HANDLING PVC PIPING PVC (Polyvinyl Chloride) and CPVC To prevent injury or death lifting (Chlorinated Polyvinyl Chloride) are equipment capacity shall exceed unit vulnerable attack certain weight by an adequate safety factor. chemicals. Polyolester (POE) oils Always test-lift unit not more than 24 used with R-410A...
Page 9
1. Startup and service must be performed CAUTION Factory Trained Service Technician. COIL CLEANING 2. The unit is for outdoor use only. See Do not clean DX refrigerant coils with General Information section for more hot water or steam. The use of hot unit information.
CB Series Feature String Nomenclature Model Options Unit Feature Options CB - B - 060 - 3 - B - 1 : B D 0 0 D A 0 CB Base Model and Features Descriptio n BASE MODEL FEATURE 2: REFRIGERATION SERIES AND GENERATION OPTIONS 0 = Standard - Split System Air Conditioner...
General Description WARNING AAON CB Series condensing units have SHARP EDGES been designed for outdoor installation only. Startup and service must be performed by a Coils and sheet metal surfaces Factory Trained Service Technician. present sharp edges and care must...
The warranty card must be completed in full migration. This means the compressor may and returned to AAON not more than 3 cool down and liquid refrigerant may months after the unit is delivered. accumulate in the compressor. Since the...
WARNING Note: Multiple Systems with Multiple Thermostats COMPRESSOR CYCLING When several heating and cooling split systems are used to condition a space all 5 MINUTE MINIMUM OFF TIME thermostat switches must be set in either prevent motor overheating heating mode, cooling mode or off. Do not compressors must cycle off for a leave part of the systems switched to the minimum of 5 minutes.
When the unit is in place, Installation remove the dolly or lifting device. Make sure the unit is properly seated and level. AAON equipment has been designed for quick and easy installation. Locating Unit CB Series condensing units are designed for...
corner of the unit is recommended for locations, it is recommended that the unit be service. elevated to allow unobstructed drainage and airflow. Table 1 - Recommended Elevation Minimums Design Suggest Minimum Temperature Elevation 3” +15 F and above 8” -5...
Protect the branch circuit in accordance with Electrical Verify the unit nameplate agrees with the code requirements. The unit must be power supply. Connect power and control electrically grounded in accordance with field wiring as shown on the unit wiring local codes, or in the absence of local codes, diagram provided with the unit.
9825i2 Thermostat motor rotation and check blower motor ® amperage listed on the motor nameplate is Honeywell VisionPRO IAQ Thermostat not exceeded. AAON Mini Controller CAUTION Three phase voltage imbalance will cause motor overheating premature failure. Wire control signals to the unit’s low voltage terminal block located in the controls compartment.
Equivalent Line Length A moisture-indicating sight glass may be All line lengths discussed in this manual, field installed in the liquid line to indicate unless specifically stated otherwise, are the occurrence of premature flashing or Equivalent Line Lengths. The frictional moisture in the line.
If the velocity of refrigerant in the liquid line Suction Line Routing is too great, it could cause excessive noise or Pitch the suction line in the direction of flow piping erosion. recommended (about 1 foot per 120 feet of length) to maximum velocities for liquid lines are 100 maintain oil flow towards the compressor, fpm from the condenser to a receiver tank to...
A double riser used for heat pump operation works differently than that described above. The specific volume (ft /lb) of refrigerant at the discharge temperature (heating mode line conditions) is significantly lower than specific volume suction temperature (cooling mode line conditions). To compound the issue, the capacity in heating mode is lower than the capacity in cooling mode.
Hot Gas Reheat Field piping between the condensing unit The AAON modulating hot gas reheat system diverts hot discharge gas from the and the evaporator is required. condenser to the air handling unit through...
Predetermined Line Sizes diameters to ensure that this method is To aid in line sizing and selection, AAON applicable to a particular case. Do not has predetermined line sizes for the liquid, assume that these line sizes are appropriate...
Page 24
When to Use Predetermined Line Sizes section. Do not assume that these line sizes are appropriate for every case. Consult ASHRAE – Handbook Refrigeration generally accepted system piping practices. The AAON Refrigerant Piping Calculator in Ecat32 can be used for job specific line sizing.
** Hot Gas Reheat line Figure 6 - Riser height versus total equivalent line length Note: Figure 6 is for R-410A split system applications with two step compressor CB-024 through CB-060 units. The region of acceptable riser height is the lighter area. Select the corresponding predetermined line size from Table 2 above.
Startup CAUTION (See back of the manual for startup form.) COMPRESSOR ROTATION WARNING Scroll compressors are directional and will be damaged by operation in ELECTRIC SHOCK the wrong direction. Low pressure switches on compressors have been Electric shock hazard. Shut off all disconnected after factory testing.
Units equipped with hot gas bypass must Charging Refrigerant & Adjusting Refrigerant Charge have the hot gas bypass valve closed to get The unit comes with full charge based on a the proper charge. 25 foot line set. Charging a system in the field must be based on determination of Units equipped with hot gas reheat must be liquid sub-cooling and evaporator superheat.
Subtract measured liquid line evaporator superheat within temperature from the saturated temperature temperature range as shown in Table 3 (high to determine the liquid sub-cooling. superheat results in increased sub-cooling) Compare calculated sub-cooling to Table 3 Correct an overcharged system by reducing below for the appropriate unit type and the amount of refrigerant in the system to options.
For units equipped with low ambient The unit will have to be checked for proper refrigerant flood back option being charged operation once the ambient temperature is when the ambient temperature is cold: above 80°F. Once enough charge has been added to get the evaporator superheat and sub-cooling values to the correct setting, more charge CAUTION...
Compressor Operation The compressors must be off for a minimum of 5 minutes and on for a minimum of 5 Unit operations should be controlled with minutes. Short cycling of the compressors thermostat, or unit controller, never at the can causes undue stress and wear. main power supply, except for emergency, servicing, or complete shutdown of the unit.
High Voltage Terminals A1 & A2 Alarm Relay Out M1 & M2 Contactor Control Voltage N Control Voltage L U1 & U2 Digital Unloader Solenoid V1 & V2 Vapor Injection Solenoid WARNING To avoid damaging the compressor Figure 7 - Variable Capacity Compressor controller, DO NOT connect wires to Controller terminals C3, C4, T3, T4, T5, or T6.
Variable speed condenser fan head pressure control is a low ambient head pressure AAON head pressure control units can control option that sends to an electronically operate down to 35°F ambient temperature. commutated motor a variable signal in...
The low ambient system maintains normal head pressure during periods of low ambient LAC Valve by restricting liquid flow from the condenser The Low Ambient Control (LAC) valve is a to the receiver, and at the same time non-adjustable three valve that bypassing hot gas around the condenser to...
Condenser Flooding Compressor Lockouts In order to maintain head pressure in the Some units include adjustable compressor refrigeration system, liquid refrigerant is lockouts. The compressor lockout in the kept in the condenser to reduce condenser picture below can be set to any temperature surface.
E-Coated Coil Cleaning Maintenance Documented routine cleaning of e-coated (See back of the manual for maintenance coils is required to maintain coating log.) warranty coverage. At least once each year, a qualified service technician should check out the unit. This WARNING includes reading and recording suction Electric shock hazard.
Page 38
and cleaning, has been approved for use on CAUTION e-coated coils to remove mold, mildew, dust, soot, greasy residue, lint, and other High velocity water from a pressure particulate: washer or compressed air should only be used at a very low pressure Enviro-Coil Concentrate, Part Number H- to prevent fin and/or coil damages.
Check Replacement Parts compressor operation, rotation, amperage Parts for AAON equipment may be obtained and voltage to the unit nameplate (check the from your local AAON representative. amperage on the load side of the compressor Reference the unit serial number and part contactor).
CB Series Startup Form Date:______________ Job Name:_____________________________________________________________________ Address:______________________________________________________________________ Model Number:_________________________________________________________________ ______________________________________________________________________________ Serial Number:_____________________________________________ Tag:_______________ Startup Contractor:______________________________________________________________ Address:__________________________________________________ Phone:_____________ _________________________________________________________ Pre Startup Checklist Installing contractor should verify the following items. 1. Is there any visible shipping damage? 2. Is the unit level? 3.
Page 53
Refrigeration System 1 - Heating Mode (Heat Pump Only) Saturated Line Pressure Sub-cooling Superheat Temperature Temperature Discharge Suction Liquid Air-Cooled Condenser Fan Alignment_____ Check Rotation_____ Nameplate Amps________ Number...
Page 54
This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor to document any service, repair or adjustments. AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts.
Literature Change History November 2009 Update of manual formatting to match with other IOMs and adding variable capacity scroll compressor information. April 2012 Added oil drip note below piping diagrams. Updated the Startup Form. May 2012 Updated the Table of Contents. March 2013 Update of the manual revising Table S1 - Sub-Cooling and Superheat, adding Table S2 - Performance Testing Air Flow Setpoints, adding information about compressor cycling.
R57611 · Rev. A · 161221 (ACP J00187) It is the intent of AAON to provide accurate and current product information. However, in the interest of product improvement, AAON reserves the right to change pricing, specifications, and/or design of its product without notice, obligation, or liability.