Siemens SIMATIC ET 200SP Manual page 39

Ha digital input module di 16x24vdc
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Diagnostics mes‐
Error
sage
code
Inconsistent pa‐
123
rameter assign‐
ment
Retentive memory
154
in carrier module
defective
Retentive memory
155
in the terminal
block defective
Only the terminal blocks (TB 45 ...) are suitable for use with I/O modules in IO redundancy.
1
Maintenance events
A maintenance event is generated for each maintenance required identified. The MT LED
lights up on the module.
Maintenance messages do not have a direct influence on the functions of the module or digital
inputs.
Table A-2
Maintenance messages, their meaning and possible remedies
Maintenance
Error
message
code
Redundancy part‐
120
H
ner has different
hardware/firm‐
ware version
IO redundancy
121
H
warning
Retentive memo‐
154
H
ry in carrier mod‐
ule defective
Retentive memo‐
155
H
ry in the terminal
block defective
Digital Input Module DI 16x24VDC HA (6DL1131-6BH00-0PH1)
Manual, 05/2017, A5E39265608-AA
Assignment
Module
Errors in the redundancy parameters sent
H
to the module
Module
An error of the memory block on the adapt‐
H
er module was detected during startup
Module
An error of the memory block on the termi‐
H
nal block was detected during startup
Assignment
Meaning / Cause
Module
The redundantly configured and intercon‐
nected I/O modules are not compatible
Module
Unable to correctly communicate with the
partner module
Module
Fault detected in the data block on the carri‐
er module during operation
Module
An error of the memory block on the terminal
block was detected during operation
Drivers, parameters, diagnostics messages and address space
A.4 Diagnostics messages and maintenance events
Meaning
Remedy
Check the parameter assign‐
ment
Replace carrier module
Replace terminal block
Remedy
Check the operating status and
firmware version of the mod‐
ules and replace modules or
perform a firmware update.
● Check the redundancy
connection
● Check the redundant
modules
● Check and replace terminal
block if necessary
Replace carrier module
Replace terminal block