Siemens SIMATIC ET 200SP Manual page 28

Ha digital input module di 16x24vdc
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications
Article number
● horizontal installation, max.
● vertical installation, min.
● vertical installation, max.
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Derating curve
The following figure shows the load current derating with horizontal and vertical mounting
positions.
3,00
2,50
2,00
1,50
1,00
0,50
0,00
-40
Cycle time
The cycle time describes the time slice in which signals from the inputs are acquired and
processed. The cycle time of the I/O module is 1 ms (250 μs for time stamping).
Minimum pulse length
In order for a pulse or an edge transition to be reliably detected by the I/O module, the signal
status must be active for at least the duration of the minimum pulse length.
In non-redundant mode, the minimum pulse length is greater than the input delay and greater
than the cycle time.
In IO redundancy mode, the minimum pulse length is greater than the input delay and greater
than the cycle time + 50 ms.
28
-20
0
20
6DL1131-6BH00-0PH1
70 °C
-40 °C
60 °C
22.5 mm
115 mm
138 mm
135 g
40
60
80
Digital Input Module DI 16x24VDC HA (6DL1131-6BH00-0PH1)
Total current I / A
Horizontal mounting position
Total current I / A
Horizontal mounting position
Manual, 05/2017, A5E39265608-AA