Plena Voice Alarm System | Installation and User Instructions | Operation
27.4

Exit the emergency state

Exit (reset) the emergency state by pushing the EMG
Reset button on the voice alarm controller and the
remote controls (see figure 27.3). The emergency state
can also be reset with the Emergency Reset button on
the fireman's panel. In order to reset the emergency
state, it first must be acknowledged (see section 27.3).
Fault
EMG
Ack
Reset
figure 27.3: EMG Reset button
27.5

Distribute live speech

27.5.1 Introduction
Proceed as follows to distribute live speech:
1 Select zones (see section 27.5.2).
2 Make announcement (see section 27.5.3).
Bosch Security Systems | 2006-06 | 9922 141 10377 en
Zone select
Zone1
Zone2
27.5.2 Select zones
Select the zones to which the live speech must be
distributed with the Zone select buttons on the front of
the voice alarm controller or the remote controls (see
figure 27.4). A red LED indicates the zones to which the
live speech is distributed.
If the indicator of a Zone select button is off, the
zone is not selected. Push the button to select the
zone.
If the indicator of a Zone select button is on, the
zone is selected. Push the button to deselect the zone.
Note
If no additional action is taken within
10 seconds after the last Zone select button has
been pushed (for example closing the PTT
switch), the zone selection is cancelled.
Fault
EMG
Ack
Reset
figure 27.4: Zone select buttons
To select all zones, push the All call buttons on the front
of the voice alarm controller or the remote controls (see
figure 27.5).
Alert message
Alarm message
EMG mic
figure 27.5: All call button
en | 92
Zone select
Zone1
Zone2
All call
Indicator test