Plena Voice Alarm System | Installation and User Instructions | IEC60849
IEC60849 - 7.2 Records to be kept
table 18: IEC60849 - 7.2 Records to be kept
Requirement
Installation, logbook and maintenance records
shall be kept by the end-user and/or
maintenance company contracted by the end-
user in accordance with relevant international
and national standards. These shall comprise
as a minimum:
a
Installation
1
Details of the locations of all items of the
equipment.
2
"as installed" performance measurements
of the system including:
Measured loudspeaker loading per
circuit in emergency mode.
Settings of any adjustable items within
the system, including the output level
of power amplifiers.
Sound pressure levels.
Intelligibility measurements.
b
Log book. A stiff covered log book shall be
kept, in which all usage of the system and all
fault occurrences should be recorded,
together with all available automatically
produced records, to include:
1
Dates and times of usage of the system.
2
Details of tests and routine checks carried
out.
3
Time and date of each fault occurrence.
4
Details of the fault found and the
circumstances of it being found (for
example during routine maintenance).
5
Action taken to rectify or remedy.
6
Date, time and name of person in charge of
the system.
7
Countersignature of the responsible
person, if any faults occurred or have been
rectified.
Bosch Security Systems | 2006-06 | 9922 141 10377 en
Compliance
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the person nominated by the
person or body, having control of the premises
(see 4.2).