Dimplex LA 6S-TUR Installation And Operating Instructions Manual page 27

Air-to-water heat pump for outdoor installation

Advertisement

Available languages

Available languages

LA 6S-TU - LA 6S-TUR
9
Heat output coefficient of performance (COP)
9.1
Heat output / COP
1. For air temperatures between -22°C and -5°C, flow temperature increasing from 45°C to 60°C.
2. This data indicates the size and capacity of the system according to EN 14511. For an analysis of the conomic and energy efficiency of the system, other parameters, in particular
the defrosting capacity and regulation, should also be taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for care, commissioning
and operation can be found in the relevant sections of the installation and operation instructions. The specified values have the following meaning, e.g. A7/W35: outside air tem-
perature 7°C and heating water flow temperature 35°C.
3. The heat output and COP is reduced by approx. 5 % in lower operation.
4. The maximum sound pressure level under full load can increase by up to 5 dB(A), depending on the installation location.
5. The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
6. see CE declaration of conformity
7. The heat circulating pump and the heat pump manager must always be ready for operation.
1
Type and order code
2
Design
Heat source
2.1
Model
2.2
Controller
2.3
Installation location
2.4
Thermal energy metering
2.5
Performance levels
3
Operating limits
3.1
Heating water flow / return
1
3.2
Air (heating)
3.2
Cooling water flow
3.3
Air (cooling)
2
4
Flow
/ sound
4.1
Heating water flow / internal pressure differential
Nominal flow according to EN 14511 with A7 / W35...30
4.2
Minimum heating water flow rate
4.3
Cooling water flow rate / internal pressure differential
4.4
Nominal flow rate in accordance
with EN 14511
Minimum cooling water flow rate
4.5
Sound power level according to EN 12102
Normal operation / reduced operation
4.6
Sound pressure level at a distance of 10 m (air outlet side)
Normal operation / reduced operation
4.7
Air flow
5
Dimensions, weight and filling quantities
5.1
Device dimensions without connections
5.2
Device connections for heating
5.3
Weight of the transportable unit(s) incl. packaging
5.4
Refrigerant / total filling weight
5.5
GWP value / CO
equivalent
2
5.6
Refrigeration circuit hermetically sealed
5.7
Lubricant / total filling weight
5.8
Volume of heating water in device
www.dimplex.de
with A-7 / W35
with A2 / W35
with A7 / W35
with A7 / W45
with A10 / W35
1
with A7 / W45...40
with A7 / W55...47
A35 / W18...23
3 4
3 4
Normal operation
452163.66.65 · FD 9702
2
kW / ---
kW / ---
kW / ---
kW / ---
kW / ---
°C
°C
°C
°C
m³/h / Pa
m³/h / Pa
m³/h / Pa
m³/h / Pa
m³/h / Pa
m³/h / Pa
dB(A)
5
dB(A)
m³/h
H x W x L mm
inches
kg
Type / kg
--- / t
Type / litres
Litres
English
EN 14511
4,0 / 2,9
5,1 / 3,8
6,4 / 4,6
6,1 / 3,5
6,7 / 4,7
LA 6S-TUR
Air
Reversible
WPM wall-mounted
Outdoors
Integrated
1
up to 60 ± 2 / from 18
-22 to +35
+7 to +20
+15 to +45
1,15 / 12000
1,08 / 10600
0,66 / 4000
0,66 / 4000
0,8 / 6000
0,8 / 6000
56 / 52
28 / 24
2700
945 x 1350 x 600
G 1" A
185
R410A / 3,4
2088 / 7
yes
Polyolester (POE) / 0.7
1,9
EN-11