Siemens RUGGEDCOM RX1400 Installation Manual page 39

Hide thumbs Also See for RUGGEDCOM RX1400:
Table of Contents

Advertisement

Test
a
Siemens-specified severity levels
IEEE 1613 EMC Type Tests
NOTE
The RX1400 meets Class 1 requirements for copper ports.
Test
IEEE 1613
Dielectric Strength
Fast Transient (SWC)
Oscillatory (SWC)
IEEE 1613.1/
Damped Oscillating
IEC 61000-4-10
Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
IEC 60068-78
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
IEC 61850-3:2013
Description
DC Power Ports
Description
HV Impulse
Earth Ground Ports
Radiated RFI
ESD
Enclosure Contact
Magnetic Field
Description
Cold Temperature
Cold Storage
Dry Heat
Dry Heat Storage
Humidity (Damp Heat, Steady State)
Vibration
Shock
Seismic
Change of Temperature
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Enclosure ports
Enclosure Air
Enclosure Ports
100 A/m for 1 s (100 kHz and 1 MHz)
Test Ad
Test Ab
Test Bd
Test Bb
Test Db
95% (non-condensing), 55 °C (131 °F), 6 cycles
5 Cycles (-40 to 85 °C or -40 to 185 °F)
Severity
Test Levels
Levels
5 kV
Test Levels
5 kV (Fail-Safe Relay Output)
5 kV
2 kVAC
1.5 kVDC
+/- 4 kV @ 2.5 kHz
+/- 4 kV
2.5 kV common mode @1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
35 V/m
+/-2 kV, +/-4 kV, +/- 8 kV
+/-4 kV, +/-8 kV, +/-15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
-40 °C (-40 °F), 16 hours
85 °C (185 °F), 16 Hours
85 °C (185 °F), 16 hours
10 days @ 55 °C (131 °F)
and 93% relative humidity
2 g @ 10-150 Hz
30 g @ 11 mS
Method A, Class 2