Tag Data Link Settings - Omron CJ2-CPU Connection Manual

E3z-series io-link photoelectric sensor
Hide thumbs Also See for CJ2-CPU:
Table of Contents

Advertisement

6.4. Tag Data Link Settings

The I/O data (process data) for Photoelectric Sensor are allocated to the tag data links for
Slave Terminal.
The following shows the content of the tag data link settings for Slave Terminal.
D10000
(PLC to Slave Terminal)
D10003
■Output area (PLC to Slave Terminal)
Address
D10000
0 to 15
D10001
0 to 15
D10002
0 to 15
D10003
0 to 15
■Input area (Slave Terminal to PLC)
Address
0 to 15
D10100
0 to 15
D10101
0 to 15
D10102
0 to 15
D10103
Output area
8 bytes
Bit
Port 1 Output Data01
Port 2 Output Data01
Port 3 Output Data01
Port 4 Output Data01
Bit
Slave Terminal Status
0 to 3 -
4 Slave Terminal Observation
5 Slave Terminal Minor Fault
6 Slave Terminal Partial Fault
7 Slave Terminal Major Fault
8 to 13 -
14 Error Detection Flag
15 I/.O Refresh Flag
I/O Port Status
0 Port1 IN Data Enable
1 Port2 IN Data Enable
2 Port3 IN Data Enable
3 Port4 IN Data Enable
4 to 13 -
14 Communication Module Error
15 I/O Power On
Port1_2 I/O Port Error Status
0 Port1 Communication Error
1 Port1 Short Error
2 Port1 Compare Error
3 Port1 Device IO Size Error
4 Port1 Device Error
5 Port1 Device Information
6 Port1 PDO Error
7 -
8 to 15 Port2 Communication Error (Same status as for Port 1)
Port3_4 I/O Port Error Status
0 to 7 Port3 Communication Error (Same status as for Port 1)
8 to 15 Port4 Communication Error (Same status as for Port 1)
6.Communications Settings
Input area
D10100
(Slave Terminal to PLC)
16 bytes
D10107
Function name
Function name
10