Emi; Laser Safety; Installation Tools - HP FlexFabric 5950 Series Installation Manual

Hide thumbs Also See for FlexFabric 5950 Series:
Table of Contents

Advertisement

Substance
NOTE:
Dust diameter ≥ 5 μm
The equipment room must also meet limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in
Table 3 Harmful gas limits in the equipment room
Gas
SO
2
H
S
2
NH
3
Cl
2

EMI

All electromagnetic interference (EMI) sources, from outside or inside of the switch and application
system, adversely affect the switch in the following ways:
A conduction pattern of capacitance coupling.
Inductance coupling.
Electromagnetic wave radiation.
Common impedance (including the grounding system) coupling.
To prevent EMI, use the following guidelines:
If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE)
to filter interference from the power grid.
Keep the switch far away from radio transmitting stations, radar stations, and high-frequency
devices.
Use electromagnetic shielding, for example, shielded interface cables, when necessary.
To prevent signal ports from getting damaged by overvoltage or overcurrent caused by lightning
strikes, route interface cables only indoors.

Laser safety

WARNING!
• The switch is a Class 1 laser device.
• Do not stare into any fiber port when the switch has power. The laser light emitted from the optical
fiber might hurt your eyes.

Installation tools

No installation tools are provided with the switch. Prepare the following tools yourself:
Phillips screwdriver.
ESD wrist strap.
Concentration limit (particles/m
Table
3
3
)
3.
Maximum concentration (mg/m
0.2
0.006
0.05
0.01
3
)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents