Event name
CJ-series Unit Restore Operation Failed
Meaning
The restore operation for a CJ-series Unit ended in an error.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
An error occurred in the Unit Configu-
ration. (when 4 is given for attached
information 1 (Error Details))
An error occurred for a Special Unit.
(when 2 is given for attached informa-
tion 1 (Error Details))
The Unit Configuration in the backup
file does not agree with the physical
Unit configuration. (when 5 is given
for attached information 1 (Error
Details))
A restart is in progress for the Special
Unit. (when 2 is given for attached
information 1 (Error Details))
The restore conditions that are
required by the Special Unit are not
met. (when 3 is given for attached
information 1 (Error Details))
The backup files are corrupted. (when
3 is given for attached information 1
(Error Details))
The CPU Unit or CJ-series Unit has
failed. (when 1 is given for attached
information 1 (Error Details))
Attached
Attached Information 1: Error Details
information
1: It was not possible to read the backup file.
2: Communications with a Special Unit failed.
3: The restore operation for a Special Unit failed.
4: The CJ-series Unit could not be detected.
5: The Unit Configuration in the backup file does not agree with the physical Unit configuration.
Attached information 2: Rack number where error was detected, 0 to 3 (when 2 or 3 is given for Error Details)
Attached information 3: Slot number where error was detected, 0 to 9 (when 2 or 3 is given for Error Details)
Attached information 4: System Information (when 2 is given for Error Details)
Precautions/
None
Remarks
* This event code occurs for unit version 1.03 or later of the CPU Unit.
NJ-series CPU Unit Hardware User's Manual (W500)
Source details
Observation
Recovery
---
Operation
Data type
---
Correction
Eliminate the error in the Unit Config-
uration.
Eliminate the error for the Special
Unit.
Make sure that the Unit Configuration
in the backup file agrees with the
physical Unit configuration.
Restore the data when there is no
restart command for the Special Unit.
Check the restore conditions in the
manual for the Special Unit and make
sure that they are met.
Format the SD Memory Card with the
Sysmac Studio and then place the
backup file on it.
If none of the above causes applies,
replace the CPU Unit or the CJ-series
Unit.
5 Troubleshooting
Event code
102E0000 hex*
I/O bus master
Detection
timing
---
Log category
Not affected.
Name
---
Prevention
Restore the data when there are no
errors in the Unit Configuration.
Restore the data when there are no
errors for the Special Unit.
Make sure that the Unit Configuration
in the backup file agrees with the
physical Unit configuration before you
attempt to restore the data.
Do not restart the Special Unit when a
restore operation is in progress. Do
not attempt to restore data during a
restart.
Check the restore conditions in the
manual for the Special Unit and make
sure that they are met.
Do not remove the SD Memory Card
or turn OFF the power supply while
the SD BUSY indicator is lit. Replace
the SD Memory Card periodically
according to the write life of the SD
Memory Card.
None
During restore
operation
System
5
5-53