5 Troubleshooting
Event name
Low Battery Voltage
Meaning
The voltage of the Battery has dropped.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
_SelfTest_LowBattery
Cause and
Assumed cause
correction
The battery voltage is low.
The battery connector has come
loose.
The Battery is missing.
Attached
None
information
Precautions/
You may loose the user data the next time that the power supply is interrupted. You can change the event level to the
Remarks
observation level. If you change the level to the observation level, recovery procedures are not required.
Event name
CPU Unit Overheat
Meaning
The temperature inside the CPU Unit exceeded the specified value.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
_SelfTest_HighTemperature
Cause and
Assumed cause
correction
The ambient operating temperature is
too high.
Attached
None
information
Precautions/
None
Remarks
* The level was changed from the observation level to the minor fault level for unit version 1.03.
5-40
Source details
Minor fault
Recovery
Continues.
Operation
Data type
BOOL
Correction
Replace the Battery.
Reconnect the connector and make
sure it is mated correctly.
Install a Battery.
Source details
Minor fault*
Recovery
Continues.
Operation
Data type
BOOL
Correction
Make sure that the ambient operating
temperature stays between 0 and
55C.
• Provide enough space for good air
flow.
• Do not install the Controller above
equipment that generates a large
amount of heat, such as heaters,
transformers, or high-capacity
resistors.
• If the ambient temperature exceeds
55C, install a cooling fan or air
conditioner.
Event code
000B0000 hex
None
Detection
timing
Error reset
Log category
No affected
Name
Low Battery Flag
Prevention
Regularly replace the Battery.
Check for vibration and shock.
Install a Battery.
Event code
000C0000 hex
None
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Not affected.
Name
CPU Unit High Temperature Flag
Prevention
Make sure that the ambient tempera-
ture stays between 0 and 55C.
NJ-series CPU Unit Hardware User's Manual (W500)
Continuously
System
Continuously
System