Hobart 5359D Operation And Maintenance Manual page 56

Engine-driven generator set
Table of Contents

Advertisement

OM 2012
(3)
Overload
module
'
-
The over load module
(7) is a solid-state
device
designed
to interpret
a signal
from transfamers
(3)and
to send a signal
to the protective
monitor
module
(4,
Fig.
10) when an overload
condition
exists
in any generator
output
phase.
A pull-apart
electrical
connector
is mounted
on the overload
module
to provide
_ -.
quick-dbconnect
facilities
for all
wiring
to the module.
The overload
module
-
is equipped
with a hermetically-sealed,
reed-type
relay.
Relay
contacts
are
ncmal
ly open.
The solid-state
circuitry
is designed
to close relay
contacts
--when
output curre;lt
in ANY
phase reaches
125%
of normal
rated
output
capacity.
The closed
relaysen&
a signal
to the protective
monitor.
This signal
"gates"
the overload
SCR
(silicone-controlled
rectifier)
in the protective
monitcr
and interrupts
the load contactor
holding
circuit,
allowing
the load contactcr
to open.
The following
k a list of overload
module
characteristics:
NOTE:
The overload
protective
system will
function
when any phase
carries
123% to 127% of rated
load.
At
125%
load the moduk
will
function
in 4 minutes -
At
150%
load the module
will
function.
in 16 seconds.
'
At 200%
load the module
will
function
in 4 seconds.
NOTE:
All
times are plus cc minus 25%and
are nonadjustable.
(4)
Rectifier
A diode-bridge
ret tif ier (5) rece ives 400-H~
AC from phase C of the generatcr
output
and converts
it to a pulsating,
direct
current
for energiration
of the
load contacta
holding
coil
only.
Thb DC coil-holding
circuit
is controlled
indirectly
by controlling
the 400-H~
AC to the rectifier.
The ground
circuit
for the rectifier's
AC supply
must pass through
the relay
contacts
in the pro-
tective
monitcr
module
to ground cable
N.
Therefore,
any time a protective
device
functions
to open the protective
monitcr
relay,
the rectifier's
AC cir-
cuit
k opened.
No DC is then available
for the load contactcr
holding
coil,
hence,
the load contactor
opens.
(5)
Terminal
boards
Three
terminal
boards (2) provide
connection
facilities
fcr small
leads.
1-l
Page 32
Aug 25'85

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

90g20

Table of Contents