3.
ELECTRIC CHARACTERISTICS
Type
Compact Wall Mounted
Wall Mounted
Compact Cassette
Slim Duct
MCA : Min Circuit Amps = Max Operating Current (Full Load).
MFA : Main Fuse (Circuit breaker) Amps.
Power Supply
Model name
Hz
ASU7RLF
60
ASU9RLF
60
ASU12RLF
60
ASU18RLF
60
ASU24RLF
60
AUU9RLF
60
AUU12RLF
60
AUU18RLF
60
ARU9RLF
60
ARU12RLF
60
ARU18RLF
60
ARU24RLF
60
- (04 - 09) -
Voltage
MCA
Input Power
(V)
(A)
(W)
208 / 230
0.18 / 0.17
15 / 15
208 / 230
0.20 / 0.19
17 / 17
208 / 230
0.25 / 0.24
22 / 22
208 / 230
0.42 / 0.40
40 / 41
208 / 230
0.71 / 0.66
68 / 69
208 / 230
0.19 / 0.19
17 / 18
208 / 230
0.24 / 0.24
22 / 23
208 / 230
0.41 / 0.38
38 / 39
208 / 230
0.40 / 0.38
47 / 49
208 / 230
0.47 / 0.44
56 / 58
208 / 230
0.59 / 0.55
71 / 73
208 / 230
0.89 / 0.83
109 / 111
Indoor Rated
FLA
(A)
0.14 / 0.13
0.16 / 0.15
0.20 / 0.19
0.34 / 0.32
0.57 / 0.53
0.15 / 0.15
0.19 / 0.19
0.32 / 0.30
0.32 / 0.30
0.37 / 0.35
0.47 / 0.44
0.71 / 0.66
4. INDOOR UNITS