3-2.

THE EXAMPLE OF CALCULATION

3-2-1.

COOLING EXAMPLE

EXAMPLE 1
Outdoor unit
Indoor unit 1
Room 1
Design conditions
Design temperature
Indoor : 75°F DB / 63°F WB (23.9°C DB / 17.2°C WB)
Outdoor : 86°F DB (30°C DB)
Pipe length
Main piping length : L1=32.8ft. (10m)
Branch piping length : L2=32.8ft. (10m)
Operation mode: Cooling
Selection of indoor unit
A-1 Cooling heat load
A-2 Indoor unit models
A-3 Rated capacity (TC
)
in
r
A-4 Total rated capacity ∑(TC
)
in
Connecting indoor unit
A-5
capacity (Cp)
Capacity change rate by
A-6
suction temperature of
indoor unit
Total capacity at design
A-7
temperature ∑(TC
)
in
d
Calculate the Maximum capacity of outdoor unit
B-1 Outdoor unit model
B-2 Rated capacity (TC
)
out
r
B-3 Capacity change rate by temperature conditions
B-4 Capacity change rate by indoor units connecting capacity
B-5 Compensation coefficient of pipe length
B-6 Maximum capacity of outdoor unit (TC
Decide system capacity
C-1 System capacity
Calculate actual capacity of each indoor unit
Actual capacity of each indoor
Btu
unit
Actual capacity of all indoor units is larger than cooling heat load of each room.
(When the connecting capacity for indoor unit is 100% or more)
Main Piping length, L1=32.8ft. (10m)
Branch
box
Indoor unit 2
Indoor unit 3
Indoor unit 4
Room 2
Room 3
Room 4
Room 1
Room 2
Room 3
Btu
5800
5800
5800
ASU7
ASU7
ASU7
Btu
7000
7000
7000
Btu
r
56000 / 48000 = 117% (80%≤Cp≤130%)
Btu
Btu
)
Btu
out
c
Room 1
Room 2
Room 3
5970
5970
5970
- (02 - 05) -
Branch Piping length, L1=32.8ft. (10m)
Branch
Branch
box
box
Indoor unit 5
Indoor unit 6
Room 5
Room 6
Room 4
Room 5
Room 6
5800
5800
5800
ASU7
ASU7
ASU7
7000
7000
7000
7000 x 8 = 56000
46.1 / 48.0 = 0.960
56000 x 0.960 = 53760
AOU48RLXFZ
48000
47.4 / 48.0 = 0.988
52.4 / 48.0 = 1.092
0.98 x 0.942 = 0.923
48000 x 0.988 x 1.092 x 0.923 = 47800
Btu
47800
Room 4
Room 5
Room 6
Room 7
5970
5970
5970
5970
Indoor unit 7
Indoor unit 8
Room 7
Room 8
Remark
Room 7
Room 8
5800
5800
ASU7
ASU7
7000
7000
Cooling
Sum of A-3
See Fig.1
(A-4) x (A-6)
Remark
Cooling
See Fig.1
See Fig.2
See 5-1.
(B-2) x (B-3) x (B-4) x (B-5)
Remark
Smaller one of (A-7)
and (B-6)
Room 8
Remark
5970
(A-3) x (C-1) / (A-4)
2. MODEL SELECTION