Fujitsu AOU48RLXFZ Design & Technical Manual page 246

Hybrid flex inverter system
Table of Contents

Advertisement

PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on-
site work. The air conditioner is set to the Peak cut mode when closing the contact input of a
commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
Outdoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Use the following parts and construct a circuit as shown above.
Input Signal···ON : Peak cut mode, Input Signal···OFF : Normal operation
*Set the "Peak cut mode" level, refer to "5.FUNCTION SETTING".
ON
Input Signal
OFF
ON
Peak cut mode
OFF
Parts (Optional)
Parts name
Model name
Connected unit
Ex.) Switch
Contact capacity : 24VDC or more, 10mA or more.
*33ft. (10m)
Signal
Field supply
External connect kit
UTY-XWZXZ3
- (06 - 92) -
6. SYSTEM DESIGN