Daikin RXYQ5-48MAY1 Service Manual page 33

R410a heat pump 50hz
Table of Contents

Advertisement

Specifications
Ceiling Mounted Cassette Type (Double Flow)
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Panel Color
Decoration
Dimensions: (H×W×D)
Panels
(Option)
Air Filter
Weight
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
22
FXCQ50MVE
kcal/h
5,000
Btu/h
19,900
kW
5.8
kW
5.6
kcal/h
5,400
Btu/h
21,500
kW
6.3
Galvanized Steel Plate
mm
305×990×600
mm
2×10×1.5
2×0.145
2D17K1AA1
Sirocco Fan
W
20×1
m³/min
12/9
cfm
424/318
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
mm
VP25
mm
(
External Dia. 32
)
Internal Dia. 25
kg
32
dBA
34/29
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
R410A M Series
BYBC50G-W1
White (10Y9/0.5)
mm
53×1,245×680
Resin Net
(with Mold Resistant)
kg
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
these values are normally somewhat higher as a result of ambient conditions.
FXCQ63MVE
6,300
25,000
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
Galvanized Steel Plate
305×1,175×600
2×10×1.5
2×0.184
2D17K2AA1VE
Sirocco Fan
30×1
16.5/13
582/459
Direct Drive
Microprocessor Thermostat
Microprocessor Thermostat
for Cooling and Heating
for Cooling and Heating
Glass Wool/Urethane Foam
Glass Wool/Urethane Foam
φ9.5 (Flare Connection)
φ9.5 (Flare Connection)
φ15.9 (Flare Connection)
φ15.9 (Flare Connection)
VP25
(
External Dia. 32
)
(
External Dia. 32
Internal Dia. 25
35
37/32
Fuse, Thermal Protector for
Fuse, Thermal Protector for
Fan Motor
Electronic Expansion Valve
Electronic Expansion Valve
R410A M Series
R410A M Series
BYBC63G-W1
BYBC125G-W1
White (10Y9/0.5)
White (10Y9/0.5)
53×1,430×680
Resin Net
(with Mold Resistant)
(with Mold Resistant)
9.5
Operation Manual,
Operation Manual,
Installation Manual, Paper
Installation Manual, Paper
Pattern for Installation,
Pattern for Installation,
Washer for Hanging
Washer for Hanging
Brackets, Clamp Metal,
Brackets, Clamp Metal,
Drain Hose, Insulation for
Drain Hose, Insulation for
Fitting, Washer Fixing
Fitting, Washer Fixing
Plates, Sealing Pads,
Plates, Sealing Pads,
Clamps, Screws, Washers.
Clamps, Screws, Washers.
3D039413
FXCQ80MVE
FXCQ125MVE
8,000
12,500
31,800
49,600
9.3
14.5
9.0
14.0
8,600
13,800
34,100
54,600
10.0
16.0
Galvanized Steel Plate
305×1,665×600
305×1,665×600
2×10×1.5
2×10×1.5
2×0.287
2×0.287
3D17K2AA1
3D17K2AB1
Sirocco Fan
Sirocco Fan
50×1
85×1
26/21
33/25
918/741
1,165/883
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
φ9.5 (Flare Connection)
φ15.9 (Flare Connection)
VP25
VP25
)
(
External Dia. 32
Internal Dia. 25
Internal Dia. 25
47
39/34
44/38
Fuse, Thermal Protector for
Fan Motor
Fan Motor
Electronic Expansion Valve
R410A M Series
BYBC125G-W1
White (10Y9/0.5)
53×1,920×680
53×1,920×680
Resin Net
Resin Net
(with Mold Resistant)
12
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications
Si39-407
)
48
12

Hide quick links:

Advertisement

Table of Contents
loading