Daikin RXYQ5-48MAY1 Service Manual page 135

R410a heat pump 50hz
Table of Contents

Advertisement

Field Setting
3.1.3 Simplified Remote Controller
BRC2A51
1. Remove the upper part of remote controller.
2. When in the normal mode, press the [BS6] BUTTON ( ) (field set), and the FIELD SET
3. Select the desired MODE No. with the [BS2] BUTTON ( ) (temperature setting ) and the
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been
5. Push the [BS9] BUTTON ( ) (set A) and select FIRST CODE NO.
6. Push the [BS10] BUTTON ( ) (set B) and select SECOND CODE NO.
7. Push the [BS7] BUTTON ( ) (set/cancel) once and the present settings are SET.
8. Push the [BS6] BUTTON ( ) (field set) to return to the NORMAL MODE.
9. (Example) If during group setting and the time to clean air filter is set to FILTER
124
MODE is entered.
[BS3] BUTTON ( ) (temperature setting ).
selected), push the [BS8] ( ) BUTTON (unit No.) and select the INDOOR UNIT NO. to be
set. (This operation is unnecessary when setting by group.)
CONTAMINATION - HEAVY, SET MODE NO. to "10", FIRST CODE NO. to "0", and
SECOND CODE NO. to "02".
Si39-407
Test Operation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents