Daikin RXYQ5-48MAY1 Service Manual page 150

R410a heat pump 50hz
Table of Contents

Advertisement

Si39-407
The following settings are made by pushbutton switches on PC board.
In case of multi-outdoor unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED indication as shown below.
LED INDICATION
Outdoor-
There are the following three setting modes.
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during
"abnormal", "low noise control" and "demand control".
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
Used to check the program made in Setting mode 2.
Press BS1 (MODE button) for more than 5 sec.
Setting mode 2
Setting item selection (Set)
Setting condition
selection (Set)
Setting condition
(Contents) display
Test Operation
Setting by pushbutton switches
Page
H1P
Single-outdoor-unit
7
system
7
Master
7
Slave 1
multi
system
7
Slave 2
Setting mode 1 (H1P off)
Setting mode 2 (H1P on)
Monitor mode (H1P blinks)
Mode changing procedure
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
Push the BS1(MODE button) one time.
MODE
On
H1P
Mode changing procedure
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS1
(MODE button).
COOL/HEAT select
Preparation
alarm
Individual
Batch master
H2P
H3P
H4P
7
8
7
7
8
7
7
7
7
7
7
7
BS1
BS2
BS3
BS4
MODE
SET
RETURN
TEST
(Normal)
Setting mode 1
MODE
Off
H1P
(Set): Select mode with BS2 (SET button) in each selection step.
Setting mode 1
Press BS1(MODE button).
(Initial condition)
Low
Demand
noise
Batch slave
H5P
H6P
H7P
7
7
7
7
7
7
7
7
7
7
7
7
(Factory setting)
BS5
RESET
(V2760)
Push the BS1(MODE button)
one time.
Monitor mode
MODE
H1P
Monitor mode
Check item selection (Set)
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Press BS1
(MODE button).
(V2762)
Field Setting
Mult
H8P
7
8
9
7
Blinking
(V2761)
139